Auto-Zone CV & CV-EX
Section 4
Start-Up and Troubleshooting 4-17
Troubleshooting
The following is a guide to assist in troubleshooting the CV and CV-EX systems. It is
provided as a systematic approach to determining and resolving common system
problems.
General Communications
No CV Units are communicating
Is the CommLink connected and plugged in?
For CV is the CommLink jumper set for single loop operation? See Figure 4-3
For CV-EX systems is the CommLink jumper set for multiple loop operation? See
Figure 4-3
Are Comm Loop voltages correct? See the Comm Loop troubleshooting section.
Is the Comm Loop open or shorted?
Are the CV Controller address switches set correctly? See Figure 4-7.
Are the CV Controllers powered? Check 24 VAC to the controllers.
Is the Communications Loop shorted? Check Comm Loop voltages.
Is the System Manager connected to the Communications loop?
Some CV Units are communicating but others are not:
Are the CV Controller address switches set correctly? See the addressing chart.
Are the CV Controllers powered? Check 24 VAC to the controllers.
Is the REC LED on the missing CV Controller “flickering”? See Figure 4-6 for
location of the REC LED.
Is the COMM LED on the CV Controller blinking an error code? See the Blink Code
chart.
Are Comm Loop voltages correct at the missing unit? See the Comm Loop trouble-
shooting section.