Auto-Zone CV & CV-EX
Section 3
Programming 3-11
CV Controller Force
Modes
OPERATING MODE
0) Auto 1) Occupied
2) Night 3) Fan Only
Enter Clock Mode: 0
The Constant Volume Units default to the Auto mode of
operation when first powered up. Any force modes entered
will be retained in non-volatile memory. The unit will resume
the force mode of operation anytime the power is cycled.
0) Auto
-
Use internal schedules for Day/Night
Mode
1) Occupied
-
Forced to Continuous Day or Occupied
Mode
2) Night
-
Forced to Continuous Night or
Unoccupied Mode.
3) Fan Only
- This mode disables any heating or cooling
and operates the Fan only. You can use
this mode anytime you want to manually
purge your building.