Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
7 Commissioning
83300902 1/2019-02 La
52-112
3. Preset setting pressure
If a controlled shutdown or lockout occurs during setting:
Briefly press[G] and [L/A] keys simultaneously.
Press [+] key.
Combustion manager changes to setting level.
Open test point for setting pressure and connect pressure measuring device.
Open gas isolating valve.
Briefly press [–] and [+] keys simultaneously.
The display shows E ACCESS.
Press[+] key.
Burner starts according to the sequence of operation and stops at operating point
P0 (ignition position).
Preset setting pressure determined at multifunction assembly [ch.7.1.5].
Check CO content of combustion and if necessary adjust combustion values via
gas butterfly valve setting [G].