EasyManuals Logo

Weishaupt WL20/2-C Z User Manual

Weishaupt WL20/2-C Z
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
Installation and operating instruction
Oil burner WL20/2-C Z
10 Troubleshooting
83307702 1/2019-04 La
54-80
10.1.2 Illuminated push button red
A burner fault has occurred. The burner is in lockout. Prior to resetting, the error
code can be called up and used to control the cause of the fault.
Read error code
Only 5 seconds after a fault occurred can it be been analysed and read.
Press illuminated push button for 5 seconds.
Illuminated push button briefly lights up orange.
Illuminated push button flashes red.
Count between the flashing pauses and flashing signals and note down.
Rectify cause of fault, see table.
Resetting
WARNING
Damage resulting from incorrect fault repair
Incorrect fault repair can cause damage to the equipment and injure personnel.
Do not carry out more than 2 lockout resets successively.
Faults must be rectified by qualified personnel.
Press illuminated push button for 1 second.
Red signal extinguishes.
Burner has been reset.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Weishaupt WL20/2-C Z and is the answer not in the manual?

Weishaupt WL20/2-C Z Specifications

General IconGeneral
BrandWeishaupt
ModelWL20/2-C Z
CategoryBurner
LanguageEnglish

Related product manuals