EasyManua.ls Logo

WIKA T16 - Versioning Per NAMUR NE53; 12 Accessories

WIKA T16
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN
11. Specifications / 12. Accessories
14147933.02 10/2018 EN/DE
WIKA operating instructions model T16
31
Ambient temperature range
Application Ambient temperature range Temperature class
Group II -40 °C (-40 °F) ≤ T
a
≤ +85 °C (+185 °F) T4
-40 °C (-40 °F) ≤ T
a
≤ +70 °C (+158 °F) T5
-40 °C (-40 °F) ≤ T
a
≤ +55 °C (+131 °F) T6
N / A = not applicable
11.3 Versioning per NAMUR NE53
Firmware version Comments WIKAsoft-TT Modem
V 1.0.0 First “Launch” version
of the T16
v 1.5 PU-448 (S. no. >10000) or
PU-548
For further specifications see WIKA data sheet TE 16.01 and the order documentation.
12. Accessories
Model Special features Order no.
Programming unit
Model PU-548
■
Simple operation
■
LED status display
■
Compact design
■
No further voltage supply is needed for either the
programming unit or for the transmitter
■
No driver installation needed (Windows
®
standard
drivers are used)
■
2 mm banana plug
■
Incl. 1 model magWIK magnetic quick connector
(replaces programming unit model PU-448)
14231581
Magnetic quick
connector
magWIK
■
Replacement for fine alligator clips and HART
®
terminals
■
Fast, safe and tight electrical connection
■
For all configuration and calibration processes
■
2 mm socket
■
Incl. 2 adapters (2 mm to 4 mm socket)
14026893
Adapter
■
Suitable for TS 35 per DIN EN 60715 (DIN EN 50022)
or TS 32 per DIN EN 50035
■
Material: Plastic / stainless steel
■
Dimensions: 60 x 20 x 41.6 mm (2.3 x 0.7 x 1.6 in)
3593789
Adapter
■
Suitable for TS 35 per DIN EN 60715 (DIN EN 50022)
■
Material: Steel, tin-plated
■
Dimensions: 49 x 8 x 14 mm (1.9 x 0.3 x 0.5 in)
3619851