Parameter name Default value Level Description
P4-18:Pump starts no 0 2 Displays the number of pump starts. Reset the counter by writing zero
to the parameter.
P4-19:Snoring sensitivity 90 2 Displays the amount of power that is consumed during snoring
compared to the power consumed during normal operation that
triggers a snoring event. Setting the parameter to 90 corresponds to
triggering a snoring event at 90% of normal power consumption.
P5-01:Drive fieldbus address 50 2 Drive fieldbus address
P5-03:Modbus/BACnet baud rate 0: 9.6 kbps 2 Modbus/BACnet baud rate
P5-04:Modbus /BACnet data format 0: n-1 none
parity, 1 stop
bit
2 Modbus /BACnet data format
P5-05:Comms loss timeout 1 2 Communications loss timeout
P6-13:Sump/pipe cleaning setting 1 3 Configures the cyclic occurrence of the Sump cleaning (SC) and the Pipe
cleaning (PC) function
0: Off
1: PC & SC 1
2: PC & SC 12
3: PC & SC 25
4: PC & SC 50
5: PC 12
6: PC 25
P6-16:Advanced control 0 3 Do not modify unless advised by a support technician.
P6-19:Relay output 1 7 3 Configures when relay output is open or closed.
0: Enable
1: Leakage alarm
2: Pump over temp alarm
3: High level alarm (Dig)
4: Sensor error
5: High level alarm (An)
6: Trip
7: A-Alarm
8: B-Alarm
9: Pump running
P6-20:Relay output 2 9 3 Configures when relay output is open or closed.
0: Enable
1: Leakage alarm
2: Pump over temp alarm
3: High level alarm (Dig)
4: Sensor error
5: High level alarm (An)
6: Trip
7: A-Alarm
8: B-Alarm
9: Pump running
Technical Reference
SRC 311 - SmartRun
Installation, Operation, and Maintenance Manual 55