e-SV series - Installation, Operation and Maintenance Manual 35
Piping and/or unit clogged
7.7 When switched off, the unit turns in the opposite direction
Replace the foot check valve
7.8 The unit produces excessive noise and/or vibrations
Increase the NPSH
5
available in the system
Unsuitable anchoring to the ground
Check the anchoring to the ground
Anti-vibration joints not installed
Install anti-vibration joints on the suction and
discharge sides of the unit
Foreign bodies in the unit
Remove the foreign bodies
Motor bearings worn or faulty
Replace the motor bearings
The unit does not turn freely due to a
mechanical fault
Send the unit to an authorised workshop for
testing
7.9 The unit starts up too frequently (automatic start/stop)
Incorrect priming (there are air bubbles in the
suction pipe or in the unit)
Repeat the priming procedure
Check valve locked in closed or partially closed
position
Foot check valve locked in closed or partially
closed position
Replace the foot check valve
Starter (pressure switch, sensor, etc.) set
incorrectly, or faulty
Adjust or replace the starter
Expansion vessel
no pre-charge, or
undersized, or
not installed
Pre-charge the expansion vessel, or
replace the expansion vessel with another
suitable one, or
install an expansion vessel
Contact Xylem or the Authorised Distributor
7.10 The unit never stops (automatic start/stop)
The required flow rate is greater than the one
expected
Reduce the required flow rate
Motor turns in the wrong direction
Check the direction of rotation and change it if
necessary
Pipes, on-off valves or filter clogged with
impurities
Starter (pressure switch, sensor, etc.) set
incorrectly, or faulty
Adjust or replace the starter
The unit runs but there is little or no flow rate
See the section: The thermal overload
protection triggers
5
Net Positive Suction Head