en - Original instructions
40 e-SV series - Installation, Operation and Maintenance Manual
8.5 Protection class
IP 55.
8.6 Electrical specifications
See the motor data plate.
8.7 Permitted tolerances for the supply voltage
Frequency Hz
Phase ~
No. of conductors + earth
UN, V ± %
50
1
2 + 1
220-240 ± 6
3
3 + 1
230/400 ± 10
400/690 ± 10
60
1
2 + 1
220÷230 ± 6
3
3 + 1
220/380 ± 5
380/660 ± 10
8.8 Noise level
Measured in free field at a distance of one metre from the unit, with standard Xylem motor
operating without load.
50 Hz motors
Table 6: LpA noise level, db (A)
Power, kW
2900 min
-1
1450 min
-1
0.25 0.37 0.55 0.75 1 1.5 2.2 3 4
5.5 7.5
<70
<70
11
73
15 18.5 22
75
30 - 37
74
45
78
55
84
60 Hz motors
Table 7: LpA noise level, db (A)
Power, kW
3500 min
-1
1750 min
-1
0.25 - 0.37
<70
0.55 0.75 1 1.5
<70
<70
2.2 - 3
70
<70
4
71
<70
5.5 - 7.5
73
<70
11
79
<70
15
80
<70
18.5 - 22
80
30 - 37
78
45
83
55
89

Table of Contents