8 Output Assemblies (Drive Consumes)
30 YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual
Enhanced Control (Vendor Specific Yaskawa Electric (YE) Assy) - 106 (0x6A)
Output
Instance
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
106
0
Multi-Function
Input 8
Multi-Function
Input 7
Multi-
Function Input
6
Multi-
Function Input
5
Multi-
Function Input
4
Multi-
Function Input
3
Run
Rev
Run
Fwd
1
Multi-Function
Photocoupler 2
Multi-Function
Photocoupler 1
Multi-
Function
Digital Output
–––
Fault
Reset
External
Fault
2 Speed Reference (Low Byte)
3 Speed Reference (High Byte)
4–
5–
6–
7–
Parameter Data
Run Fwd
Forward Run Command
0: Stop
1: Forward Run
Run Rev
Reverse Run Command
0: Stop
1: Reverse Run
Multi-Function Input 3
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Multi-Function Input 4
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Multi-Function Input 5
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Multi-Function Input 8
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
External Fault
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
Multi-Function Digital Output
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Multi-Function Photocoupler 1
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Multi-Function Photocoupler 2
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.

Other manuals for YASKAWA 1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA 1000 Series and is the answer not in the manual?

YASKAWA 1000 Series Specifications

General IconGeneral
Series1000 Series
CategoryDC Drives
Cooling MethodForced air cooling
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceModbus RTU
Storage Temperature-20°C to +60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Input Voltage200-240V AC, 380-480V AC