EasyManuals Logo

YASKAWA GPD515C User Manual

YASKAWA GPD515C
26 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
1-21
380V
400/
415V 440V 460V
Voltage Selector
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
1ø POWER SUPPLY (SEE NOTE 11)
1CB ✱✱
GPD 515/G5
L1 L2 L3
15
16
17
12
14
13
+15Vdc
(20mA MAX)
MAN REF. IN
(0 TO ±10Vdc)
FWD
FWD
RUN/STOP
COM
SHIELD
4-20mA
(250
0 TO ±10Vdc
(20K
SEE
NOTE 4
4-20mA
0-10V
ISOLATED
AUTO
REFERENCE
SEE NOTE 6
1OL
SEE
NOTE
2
EXT. FAULT
EXT. FAULT RESET
1PB
SEE
NOTE 3
TO
TERM. 12
1R
MAN SPEED
1RH
SEE NOTE 1
AUTO
MAN
3SS
1SS
SEE
NOTE 1
1
2
3
4
5
6
7
8
11
9
REV
EXT. FAULT
FAULT RESET
AUTO/MAN
MULTI-STEP
FREQ SELECT
JOG
SPEED
COAST STOP
(BASE BLOCK)
0 VOLTS
RUN CONTACT
RY1
10
FAULT CONTACTS
RY2
RY2
18
19
20
ANALOG
OUTPUT
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
21
22
25
26
27
RY CONTACTS
CAPACITY:
1A AT 250Vac
1A AT 30Vdc
MULTI-FUNCTION
MONITOR OUTPUT
0 to +10V or
10 to +10V,
2mA MAX.
MULTI-
FUNCTION
OPEN
COLLECTOR
OUTPUTS
CAPACITY:
50mA AT 48Vdc MAX.
AC MOTOR
(T2)
(T1) (T3)
G
T1 T2 T3
(GPD515C-B041 thru -B096)
FACTORY SET FOR 460V
EARTH
GROUND
SEE NOTE 5
1OL
SEE NOTE 2
L1 L2 L3
BASIC INTERCONNECT DIAGRAM FOR 2-WIRE CONTROL
(R) (S) (T) (r)
(E)
(U) (V) (W)
2SS
REV
RUN/STOP
TERMINALS 1-8:
IF INPUT FROM RELAY CONTACTS:
RATED 30Vdc OR MORE,
100mA OR MORE
IF OPEN COLLECTOR INPUT:
RATED 35Vdc OR MORE,
100mA OR MORE
B1
B2
FOR WIRING
DYNAMIC
BRAKING
OPTION
SEE NOTE 7
1 2
COOLING
FAN
POWER
(GPD515C-A080 [CIMR-G5M20151F] AND ABOVE;
GPD515C-B041 [CIMR-G5M40151F] AND ABOVE;
GPD515C-C027 [CIMR-G5M50221F] AND ABOVE)
SEE NOTE 10
+ 1
+ 2
SEE
NOTE 9
ANALOG
OUTPUT
23
FOR OPTIONAL
DC REACTOR
SEE NOTE 8
+
+
SEQ REF
DRIVE FWD REV REMOTE
DIGITAL OPERATOR
JVOP-130
DATA
ENTER
FWD
REV
RESET
RUN STOP
JOG
LOCAL
REMOTE
MENU ESC
T1 T2 T3
(U) (V) (W)
AC MOTOR
(T2)
(T1) (T3)
ALTERNATE
MOTOR CONNECTION
33
15Vdc
(20mA MAX)
+ 3
OR
Figure 1-3. 230, 460 or 600V Interconnections - 2-Wire Control
(with parameters b1-01 = 1, b1-02 = 1, H1-01 = 24, H1-02 = 14, H1-03 = 3,
H1-04 = 4, H1-05 = 6, and H1-06 = 8 )
See Figure 1-5 for Closed-loop PG connections

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA GPD515C and is the answer not in the manual?

YASKAWA GPD515C Specifications

General IconGeneral
BrandYASKAWA
ModelGPD515C
CategoryController
LanguageEnglish

Related product manuals