YASKAWA TM.iQp.02 iQpump Drive Programming Manual 181
H1-04 0403H
Terminal S6 Function
Selection
Terminal S6 Sel
20: External Pump Fault, Normally Open, Always Detected, Ramp To
Stop
21: External Pump Fault, Normally Closed, Always Detected, Ramp
To Stop
22: External Pump Fault, Normally Open, During Run, Ramp To Stop
23: External Pump Fault, Normally Closed, During Run, Ramp To Stop
24: External Pump Fault, Normally Open, Always Detected, Coast To
Stop
25: External Pump Fault, Normally Closed, Always Detected, Coast To
Stop
26: External Pump Fault, Normally Open, During Run, Coast To Stop
27: External Pump Fault, Normally Closed, During Run, Coast To Stop
28: External Pump Fault, Normally Open, Always Detected, Fast-Stop
29: External Pump Fault, Normally Open, Always Detected, Fast-Stop
2A: External Pump Fault, Normally Open, During Run, Fast-Stop
2B: External Pump Fault, Normally Closed, During Run, Fast-Stop
2C: External Pump Fault, Normally Open, Always Detected, Alarm
Only
2D: External Pump Fault, Normally Closed, Always Detected, Alarm
Only
2E: External Pump Fault, Normally Open, During Run, Alarm Only
2F: External Pump Fault, Normally Closed, During Run, Alarm Only
30: PID Integral Reset
31: PID Integral Hold
34: PI SFS Cancel.
35: Input Level Sel
36: Option/Inv Sel 2
Selects source of speed command and sequence.
Closed = Option Card, Open = b1-01 & b1-02.
60: Motor Preheat Applies current to create heat to avoid condensation.
Closed = Apply amount of current as set in parameter b2-09.
61: Speed Search 1
When closed as a run command is given, Drive does a speed
search starting at maximum frequency (E1-04). (Current detection.)
62: Speed Search 2
When closed as a run command is given, Drive does a speed
search starting at speed command. (Current detection.)
64: Speed Search 3
67: Com Test Mode - Used to test RS-485/422 interface.
Direction determined by fwd/rev input. 3-wire control Only.
6A: Drive Enable - Closed = Drive will accept run command.
Open = Drive will not run. If running, Drive will stop per b1-03.
6B: Com/Inv Sel - Selects source of speed command and sequence
Closed = Serial Communication (R+,R-,S+,S-), Open = b1-01 & b1-02
6C: Com/Inv Sel 2
80: Hand Mode
Function Active in Stopped and Auto Mode.
Closed: Hand mode operation as defined in P1-14.
Open: Stop Mode when with no incoming run command.
Note: Input not active when b1-02 is set for 0 – Operator.
81: Disable Sleep Mode
Function Active in Auto Mode.
Closed: Disables sleep function, Feedback Drop Detection and Over
cycle protection.
Open: Sleep function, Feedback Drop Detection and Over cycle
protection enabled.
82: Sleep Activation
Active in Auto Mode.
Closed: Drive will go to sleep (External Digital Input).
Open: No function.
0 to 87 80 Programming
47
Parameter
No.
Modbus
Address
Parameter Name
Digital Operator
Display
Description
Setting
Range
Factory
Setting
Menu
Location
Page
No.