EasyManua.ls Logo

YASKAWA iQpump Series

YASKAWA iQpump Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YASKAWA TM.iQp.02 iQpump Drive Programming Manual 71
Figure 1.63
Figure 63 Output Frequency with Reduced Bias Setting
As a further example, for an inverse-acting speed command, set the bias = 100% and the gain = 0%. The minimum analog input level (0
Vdc or 4 mA) will produce a 100% speed command and the maximum analog input level (10 Vdc or 20 mA) will produce a 0% speed
command.
Figure 1.64
Figure 64 Output Frequency with Inverted Gain and Bias Settings
H3-08 Terminal A2 Signal Level
The H3-08 parameter (Terminal A2 Signal Level) allows the programmer to specify the signal that will be applied to the A2 analog input.
The A2 analog input can accept either a 0–10 Vdc or 4-20 mA signal as a reference. The iQpump drive also has a DIP switch (S1) on the
removable terminal board that must be set for the proper reference signal into the A2 analog input. The S1-2 dipswitch setting determines
the internal resistance of the A2 input while parameter H3-08 determines how the iQpump drive interprets the measured signal.
Setting Description
0 0 - 10 Vdc
2 4 - 20 mA (factory default)
3 0 - 20 mA
0V
4mA
10V
20mA
Gain = 100%
Bias = -25%
Output
Frequency
Analog Input Level
2.5V
8mA
Analog Input Signal
20mA
4mA
0V
10V
Gain = 100%
Bias = 0%
Output
Frequency
Analog Input Level
Analog Input Signal
Bias
Gain

Table of Contents

Related product manuals