EasyManua.ls Logo

YASKAWA iQpump Series

YASKAWA iQpump Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
72 YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Figure 1. 65
Figure 1. 66
Figure 65 DIP Switch S1
Table 17 DIP Switch S1
H3-09 Terminal A2 Function Selection
The A2 analog input can be programmed to perform many different functions. The setting of parameter H3-09 determines which of the
following functions the A2 analog input will perform.
Function: Frequency Bias (Setting: 0)
By setting H3-09 = “0: Frequency Bias,” the A2 analog input will serve as a bias signal to the A1 Speed Command. The effect of using
A2 for a frequency bias is that the level of the A2 analog input will be summed with the level of the Speed Command analog input (A1).
For example, if H3-02 = 100%, H3-03 = 0%, and the A2 analog input level is 1 Vdc, the Speed Command profile will look like the figure
below. If A1 = 0 Vdc the Speed Command would be 10% of the programmed maximum frequency because A1 (0 Vdc) + A2 (1 Vdc) = 1
Vdc.
Name Function Setting
S1-1 RS-485 and RS-422 terminating resistance
OFF: No terminating resistance
ON: Terminating resistance of 110 Ω
S1-2 Input method for analog input A2
OFF: 0 to 10 V (internal resistance: 20 kΩ)
ON: 4 to 20 mA (internal resistance: 250 Ω) (Default)
Setting Description
0 Frequency Bias
2Aux Reference
B PI Feedback (factory default)
D Frequency Bias 2
E Motor Temperature
16 PI Differential
1F Not Used
S1
1
Terminating
resistance
DIP Switch S1-1 located on
terminal board.
2
1

Table of Contents