3.2 Function Modules
Data Logging
3-78
15. Click the OK Button.
The Sampling and Trigger Dialog Box closed.
To automatically start logging when the power supply is turned ON, set the Start Trigger to
the following condition.
When the saving destination is set to USB memory:
Setting example: Start trigger SB006540 = ON
Note: The SB006540 register turns ON when a USB memory device is detected.
When the saving destination is set to built-in RAM disk:
Setting example: Start trigger SB000001 or SB000003 = ON
Note: The SB000001 register turns ON during the first scan of the high-speed scan.
The SB000003 register turns ON during the first scan of the low-speed scan.
In the following example, the output conditions are set to log only the data in the shaded
region.
Setting example: Condition A >= Upper limit, Condition B <= Lower limit, Compound con-
dition = OR
Click the Cancel Button to return to the Logging 1 Dialog Box without registering the set-
tings.
Example
Example
Upper limit
Lower limit
Logged data