3.2 Function Modules
Data Logging
3-84
The following example shows how the register data is given for the settings and conditions
listed below.
File Details to Output
Data No. and DATE/TIME are selected
Target Register to Log
MW00000
Status
Data No.: 000001
DATE/TIME: 2011/06/23 18:02:19
Value of MW00000 register: 100
Actual Data
The data is stored in little endian as shown below.
Example
01 00 00 00 00 00 00 00 11 00 23 06 02 18 19 00 64 00
MW00000 = 100
DATE/TIME =
2011/06/23 18:02:19
Data No. = 1