Error Classifications
Error Content Meaning
81xx
Function code error An unused function code was received or an
attempt was made to send an unused function
code.
82xx
Address setting error The data address, coil offset, input relay offset,
input register offset, or holding register offset is
out of the setting range.
83xx
Data size error The send or receive data size setting is out of the
setting range.
84xx
Circuit number setting error The circuit number is out of the setting range.
85xx
Channel number setting
error
The channel number is out of the setting range.
86xx
Node address error The node address is out of the setting range.
88xx
Communications section
error
An error response has been returned from the
communications section.
89xx
Device selection error A device that cannot be used has been selected.