YASKAWA ELECTRIC SIEP C730600 70B V1000 Option SI-EP3/V Technical Manual 51
Email Alerts Tab
The Email Alerts tab allows the user to configure four Email Fault/Alarm conditions. When the condition is true, one
email will be sent to the provided email address. Another email will not be sent until the condition becomes false and
then true again. A 30-second timer prevents emails from being sent when conditions reoccur immediately after being
removed. The timer helps limit the amount of emails sent regarding the same intermittent condition and helps to reduce
network traffic by reducing emails about reoccurring errors.
Figure 39
Figure 40 Email Alerts Tab View
Procedure: Conditional Email Set-up
1. Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value. Set
the conditions to send alerts from the “Condition” drop-down selection. If choosing only one condition and no OR
or AND are needed, set the “OR/AND” drop-down selection to “NotUsed”.
2. Enter the email address where the alert will be sent.
3. Enter the message that will appear in the email contents.
4. Enter the email subject.
5. Click the “Email Active” check box to enable the alert.
Clicking “Save to device” will save the entered information into the option.
Clicking “Cancel and reload” will cancel any pending edits and display the most recently saved settings from the option
board.