Questions and Answers

  • L
    Logan BrightSep 23, 2025
    What does CC-Link Option Flash write mode mean on YASKAWA Controller?
    • C
      Cassidy WilliamsSep 23, 2025
      CC-Link Option Flash write mode on your YASKAWA Controller indicates a CC-Link Option hardware fault. Replace the CC-Link Option.
  • Z
    zcollinsAug 25, 2025
    What to do if YASKAWA DC Drives show minor faults and alarms?
    • M
      Matthew PadillaAug 25, 2025
      If your YASKAWA DC Drives are showing minor faults and alarms, remove the cause of the alarm or minor fault to automatically reset the system.
  • E
    ericarichardsonAug 25, 2025
    How to fix option communication error on a YASKAWA V1000 Controller?
    • J
      Justin RomeroAug 26, 2025
      If you're encountering an option communication error with your YASKAWA Controller, it could be due to several reasons. First, ensure that the master controller (PLC) is receiving power. Next, verify the communication cable is properly connected and check for any faulty wiring. If noise is suspected, explore options to minimize its effects. Finally, if the problem persists after checking the wiring, consider replacing the option.
  • S
    Shawn MortonAug 26, 2025
    What to do if there is a serial communication transmission error on YASKAWA Controller?
    • H
      Hayden HamiltonAug 27, 2025
      A serial communication transmission error on your YASKAWA Controller could stem from a few issues. Begin by inspecting the communication wiring for faults like short circuits or improper connections; correct any wiring errors, remove ground shorts, and reconnect loose wires. Then, review the master side programming for errors and correct them. If problems persist, perform a self-diagnostics check. If the fault continues, consider replacing the drive.
  • C
    Craig KramerSep 23, 2025
    What does Communication ID error mean on YASKAWA Controller?
    • F
      figueroamargaretSep 23, 2025
      A Communication ID error on your YASKAWA Controller indicates a CC-Link Option hardware fault. Replace the CC-Link Option.
  • A
    Alexa GreenDec 1, 2025
    What to do if there's a serial communication transmission error in YASKAWA DC Drives?
    • R
      Rebecca ThompsonDec 1, 2025
      A serial communication transmission error in YASKAWA DC Drives may arise due to: * Faulty communication wiring: Check for wiring errors and correct them. * Short circuit or communications disconnection: Check disconnected cables and short circuits, repairing as needed. * Programming error on the master side: Check communications at start-up and correct programming errors. * Damaged communication circuitry: Perform a self-diagnostics check. If the problem persists, replace the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or your nearest sales representative. * Termination resistor of the MEMOBUS/Modbus communications is not enabled: Set DIP switch S2 to the ON position to enable the termination resistor on a drive located at ...
  • M
    Mario CastroSep 12, 2025
    What to do if YASKAWA Media Converter shows Option Communication Error?
    • C
      Cynthia NortonSep 12, 2025
      If you are experiencing an option communication error with your YASKAWA Media Converter, it could be due to several reasons: * No signal received from the PLC: Check for faulty or loose wiring and short circuits. Repair as needed. * Faulty communication cable or a short circuit: Inspect the cable for damage. * Damaged option card: If wiring is not the issue, replace the option card. * Improperly connected option card: Reinstall the option card, ensuring the connector pins are correctly aligned.
  • M
    Monica MossSep 12, 2025
    How to prevent YASKAWA Media Converter motor from overheating due to overexcitation?
    • M
      Maria SullivanSep 12, 2025
      If the YASKAWA Media Converter motor overheats due to overexcitation, it increases the motor losses and temperature, potentially causing damage if prolonged. Prevent excessive overexcitation or apply proper cooling to the motor. Reduce the excitation deceleration gain (n3-13) and set L3-04 (Stall Prevention during Deceleration) to a value other than 4.
  • H
    Holly HurstSep 5, 2025
    How to fix YASKAWA Controller CC-Link Option Communication Error?
    • A
      Amanda CortezSep 5, 2025
      If you're experiencing a CC-Link Option Communication Error with your YASKAWA Controller, here are a few things to check: * First, verify that the master controller (PLC) is still communicating. Check for faulty wiring, grounding issues, or disconnected wires and correct them. * Ensure the communication cable is properly connected. * Address potential data errors caused by noise by using Yaskawa's recommended cables or shielded alternatives, grounding the shield on both the PLC and option unit sides. Consider installing a surge absorber on the magnetic contactor coil if it's a noise source. * If the problem persists after checking these, the CC-Link Option may be damaged and need replacement.
  • M
    Michael MckinneySep 2, 2025
    What causes an Option Card External Fault on a YASKAWA Controller?
    • Z
      zjohnsonSep 3, 2025
      An Option Card External Fault on the YASKAWA Controller can occur due to: * An external fault received from the PLC when F6-03 is not set to 3; remove the cause of the external fault. * A problem with the PLC program; check the PLC program and correct any issues.

Summary

Preface and General Safety

General Safety Information

Outlines essential safety precautions and conventions for using the drive.

Application Precautions

Details important considerations for applying the drive in various scenarios.

Receiving

Mechanical Installation

Electrical Installation

Start-Up Programming and Operation

Using the Digital LED Operator

Explains the functions of keys, displays, LEDs, and screen structure.

Drive and Programming Modes

Describes the two main modes: Drive Mode and Programming Mode.

Application Selection

Details various Application Presets for common applications.

Basic Drive Setup Adjustments

Explains essential parameter settings for initial drive operation.

Auto-Tuning

Describes types, preparations, and procedures for auto-tuning the motor.

Troubleshooting

Drive Alarms, Faults, and Errors

Describes types of alarms, faults, and errors and drive responses.

Fault Detection

Details fault displays, causes, and possible solutions for various errors.

Alarm Detection

Lists alarm codes, their causes, and possible solutions.

Operator Programming Errors

Explains oPE codes, causes, and possible solutions for programming errors.

Specifications

Parameter List

Standards Compliance

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20