A.2 Single/Three-Phase 200 V Class Drives
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated
input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to
0 for HD or 1 for ND (default).
Table A.2 Power Ratings
Item Specification
Three-Phase: CIMR-Vo2A
0001 0002 0004 0006 0010 0012 0020
Single-Phase: CIMR-VoBA
<1>
0001 0002 0003 0006 0010 0012
0018
<2>
Maximum Motor Size Allowed
(HP)
<3>
ND Rating 0.13 0.25
0.5/
0.75
1.0/
1.5
2.0/
3.0
3.0
5.0
<2>
HD Rating 0.13 0.25 0.5
0.75/
1.0
1.5/
2.0
3.0 5.0
Input
Input
Current
(A)
<4>
Three-
phase
ND Rating 1.1 1.9 3.9 7.3 10.8 13.9
24.0
<2>
HD Rating 0.7 1.5 2.9 5.8 7.5 11.0 18.9
Single-
phase
ND Rating 2.0 3.6 7.3 13.8 20.2 24.0 –
HD Rating 1.4 2.8 5.5 11.0 14.1 20.6 35.0
Output
Rated Output
Capacity (kVA)
<5>
ND Rating 0.5 0.7 1.3 2.3 3.7 4.6
7.5
<2>
HD Rating 0.3 0.6 1.1 1.9 3.0 4.2 6.7
Output Current (A)
ND Rating
<6>
1.2 1.9
3.5
(3.3)
6.0 9.6 12.0
19.6
<2>
HD Rating
0.8
<7>
1.6
<7>
3.0
<7>
5.0
<7>
8.0
<8>
11.0
<8>
17.5
<8>
Overload Tolerance
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency User-adjustable 2 to 15 kHz
Max Output Voltage (V)
Three-phase power: Three-phase 200 to 240 V
Single-phase power: Three-phase 200 to 240 V
(both proportional to input voltage)
Max Output Frequency (Hz) 400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
A.2 Single/Three-Phase 200 V Class Drives
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
157
A
Specifications