B.1 Parameter Table
No. Name Description
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
A1-00 Language Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
A1-01 Access Level Selection
0: Operation only
1: User Parameters (access to parameters selected by the user)
2: Advanced Access Level
A1-02 Control Method Selection
0: V/f Control without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note: 1. Does not return to the default setting after initialization.
2. If using Open Loop Vector Control (A1-02 = 2), then Auto-Tuning
must be performed again after the drive is initialized. Refer to Auto-
Tuning on page 113 for details.
A1-03 Initialize Parameters
0: No Initialize
1110: User Initialize (First set user parameter values must be stored
using parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
5550: OPE04 Error Reset
A1-04 Password 1 Refer to V1000 Technical Manual for details.
A1-05 Password 2 Refer to V1000 Technical Manual for details.
A1-06 Application Preset Refer to V1000 Technical Manual for details.
A1-07 DriveWorksEZ Function Selection Refer to V1000 Technical Manual for details.
A2: User Parameters
Use A2 parameters to program the drive.
A2-01
to
A2-32
User Parameters, 1 to 32 Refer to V1000 Technical Manual for details.
A2-33
User Parameter Automatic
Selection
Refer to V1000 Technical Manual for details.
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01 Frequency Reference Selection 1
0: Operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2.
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
B.1 Parameter Table
168
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20

Related product manuals