Time
UP
S1-SC
S6-SC
OFF
OFF
d1-03
d1-01 (Enabled when b1-01 = 0)
L4-01
b2-01
OFF
DC Injection braking
ON
ON
ON
P2-PC
Holding brake
Fast/Slow
Output frequency
0
Frequency Detection 2
(H2-03
=
05)
Closed Closed
Open
b6-02
b6-01
Input
Output
Figure 4.9 Holding Brake Time Chart
u
Setting 7: Preset 7
Table 4.15 Preset 7: Parameters and Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-01 Frequency Reference Selection 1 0: Operator
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Drive Duty Selection 0: Heavy Duty
C6-02 Carrier Frequency Selection 2: 5 kHz
d1-01 Frequency Reference 1 6.0 Hz
d1-02 Frequency Reference 2 30.0 Hz
d1-03 Frequency Reference 3 60.0 Hz
H1-05
Multi-Function Digital Input Terminal S5
Function
3: Multi-Step Speed 1
H1-06
Multi-Function Digital Input Terminal S6
Function
4: Multi-Step Speed 2
H2-02 Terminals P1 Function Selection 37: During frequency output
L3-04
Stall Prevention Selection during
Deceleration
0: Disabled
L8-05 Input Phase Loss Protection Selection
1: Enabled
<1>
4.5 Application Selection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
103
4
Start-Up Programming
& Operation