EN 12 YASKAWA Europe TOMP_C710606_75A V1000 IP66 - Quick Start Guide
3 Electrical Installation
3 Electrical Installation
The figure below shows the main and control circuit wiring.
<1> Single-phase units do not have a L3 terminal.
<2> These terminals can be used to disable the drive output. Other than in V1000 standard drives they can NOT be used to perform safe stop according to EN60204-1 (Function
is in preparation. Contact your sales representative or YASKAWA for details).
Power
Supply
L1
L2
L3
S1
S2
S3
S4
S5
S6
B1+1+2 B2
L1
L2
L3
U/T1
V/T2
W/T3
24 V
0V
SINK
SOURCE
MA
P1
MB
MC
+24 V 8 mA
M
U
V
W
SC
P2
MP
AM
AC
PC
IG
R+
R
S+
S
H2
RP
+V
A1
A2
AC
2 kΩ
HC
H1
DC reactor
(option)
Filter
Fuses
Main
Switch
Forward/Stop
Reverse/Stop
External Fault
Fault Reset
Multi-speed 1
Multi-speed 2
Multi-function
digital inputs
(default setting)
Link
Thermal
relay
Braking
resistor
(opt)
V1000 IP66
Ground
Multi-function relay output
250 Vac / 30 Vdc (10 mA to 1A)
(default setting)
Fault
During run
Frequency agree
Photocoupler
common
Multi-function
photo-
coupler output
48 Vdc, 2 to 50 mA
(default setting)
DIP
switch S3
Shielded ground
terminal
Pulse Input
(max. 32kHz)
Multi-function analog input 1
0 to 10 V (20 k
Ω)
Multi-function analog input 2
0 to 10 V (20 k
Ω) or
0/4 to 20 mA (250
Ω)
Analog input power supply
+10.5 Vdc, max. 20 mA
Multi-function pulse / analog inputs
(default: frequency reference)
Drive Disable
inputs
Monitor outputs
(default setting)
Analog output
0 to +10 Vdc (2mA)
(Output frequency)
Pulse train output
(max. 32 kHz)
(Output frequency)
Terminal resistance
(120
Ω, 1/2 W)
Memobus comm.
RS-485/422
max. 115 kbps
Shielded
Cable
Symbols:
Use twisted pair cables.
Use shielded twisted pair cables.
Indicates the IP66 enclosure.
Indicates a main circuit terminal.
Indicates a control circuit terminal.
<1>
<2>
TOMP_C710606_75A_0_0_prePrint.pdf 44 21.12.2010 13:52:23

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled