6 Related Drive Parameters
YASKAWA ELECTRIC TOBP C730600 60C V1000 Option SI-EN3/V Installation Manual 35
F7-11
(3EF)
<5>
Gateway Address 3
Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.
Default: 1
Min: 0
Max: 255
F7-12
(3F0)
<5>
Gateway Address 4
Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.
Default: 1
Min: 0
Max: 255
F7-13
(3F1)
Address Mode at
Startup
Selects how the option address is set.
0: Static
1: BOOTP
2: DHCP
Default: 2
Range: 0 to 2
F7-14
(3F2)
Duplex Mode
Selection
Selects duplex mode setting.
0: Auto/Auto
1: Half/Half
2: Full/Full
3: Half/Auto
4: Half/Full
5: Auto/Half
6: Auto/Full
7: Full/Half
8: Full/Auto
Default:
<6>
Range: 0 to 8
F7-15
(3F3)
<7>
Communication Speed
Selection
Sets the communication speed
0: 10 Mbps (Available only with drive software version
PRG: 1012 to 1015)
10: 10 Mbps
100: 100 Mbps
Default:
<8>
Range: <8>
F7-17
(3F5)
EtherNet/IP Speed
Scaling Factor
Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-18
(3F6)
EtherNet/IP Current
Scaling Factor
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-19
(3F7)
EtherNet/IP Torque
Scaling Factor
Sets the scaling factor for the torque monitor in EtherNet/
IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-20
(3F8)
EtherNet/IP Power
Scaling Factor
Sets the scaling factor for the power monitor in EtherNet/
IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-21
(3F9)
EtherNet/IP Voltage
Scaling Factor
Sets the scaling factor for the voltage monitor in EtherNet/
IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
F7-22
(3FA)
EtherNet/IP Time
Scaling
Sets the scaling factor for the time monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
No.
(Addr. Hex)
Name Description Values