6 Related Drive Parameters
YASKAWA ELECTRIC TOBP C730600 60C V1000 Option SI-EN3/V Installation Manual 37
Table 9 Option Monitors
No. Name Description Range
U6-80 to U6-83 OPT IP ADR 1 to 4
Displays IP Address currently available;
• U6 -80: First octet
• U6 -81: Second octet
• U6 -82: Third octet
• U6 -83: Forth octet
0 to 255
U6-84 to U6-87 Online Subnet 1 to 4
Displays subnet currently available;
• U6 -84: First octet
• U6 -85: Second octet
• U6 -86: Third octet
• U6 -87: Forth octet
0 to 255
U6-88 to U6-91 Online Gateway
Displays gateway currently available;
• U6 -88: First octet
• U6 -89: Second octet
• U6 -90: Third octet
• U6 -91: Forth octet
0 to 255
U6-92 Online Speed Displays CN1 Port 1 link speed currently available.
10: 10 Mbps
100: 100 Mbps
U6-93 Online Duplex Displays CN1 Port 1 duplex setting currently available. 0: Half, 1: Full
U6-98 First Fault
Displays first option fault. Refer to Option Fault Monitors
U6-98 and U6-99 on page 52 for details.
–
U6-99 Current Fault
Displays current option fault. Refer to Option Fault
Monitors U6-98 and U6-99 on page 52 for details.
–