EasyManua.ls Logo

YOKOGAWA digitalYEWFLO Series

YOKOGAWA digitalYEWFLO Series
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<APPENDIX 7. LINK MASTER FUNCTIONS>
A7-9
IM 01F06F00-01EN
A4-2. Make the parameters in the current LAS
match the capabilities parameter in the
digitalYEWFLO as follows (Read Section 5.2
“Network Denition”):
LAS digitalYEWFLO
V(ST) > V(ST) ≥ 4
V(MID) > V(MID) 4
V(MRD) > V(MRD) 12
A4-3. Check that the digitalYEWFLO is assigned
an appropriate address. The address of
the digitalYEWFLO must not lie within
either 0x00 to 0x10 or the range of unused
(unpolled) node addresses determined by
the current LAS’s LM parameter settings,
which is V(FUN) to V(FUN) + V(NUM).
(Read Section 5.2 “Network Denition.”)

Table of Contents

Related product manuals