EasyManua.ls Logo

YOKOGAWA digitalYEWFLO Series

YOKOGAWA digitalYEWFLO Series
169 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
<APPENDIX 3. OPERATION OF EACH PARAMETER IN FAILURE MODE>
A3-6
IM 01F06F00-01EN
LCD
Display
Alarm Detail DI1 Block DI2 Block PID Block IT Block AR Block
AlarmReset
SW* (default)
AL-07
Temp.
Converter
Failure (AL-07)
<PV_D.Status>
*1
TARGET in TB’s LIMSW =
SECONDARY_VALUE
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
*2
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
Not provided
<OUT_D.Status>
*1
TARGET in TB’s LIMSW =
SECONDARY_VALUE
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
*2
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
AL-08
Temp. Sensor
Failure (AL-08)
<PV_D.Status>
*1
TARGET in TB’s LIMSW =
SECONDARY_VALUE
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Sensor Failure
*2
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
Not provided
<OUT_D.Status>
*1
TARGET in TB’s LIMSW =
SECONDARY_VALUE
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Sensor Failure
*2
Default
Bad-Non Specic
STATUS_OPTS:Propagate Fault
Forward = Active
Bad-Device Failure
AL-20
No FB
Scheduled
(AL-20)
Not provided
AL-21
RB in O/S
Mode
(AL-21)
<OUT_D.Status>
Bad-Out of Service
<OUT.Status>
Bad-Out of Service
<OUT.Status>
Bad-Out of Service
<OUT.Status>
Bad-Out of Service
Not provided
AL-22
TB in O/S Mode
(AL-22)
<PV_D.Status>
Bad-Non Specic
Not provided
<OUT_D.Status>
Bad-Non Specic

Table of Contents