6-8
<Toc> <6. Function Block Diagram and Descriptions>
IM 05D01B02-41E 1st Edition : May 31,2000-00
■ Control Output
Control output (OUTPUT1) selects the output type among the current output, voltage pulse
output, and relay contact output signal.
Preset output value is output when the operation is stopped by key operation or contact
input, which takes priority over the manual operation.
Each function can be set by the following parameters.
Setup Parameters
Function Parameter
Control output type selection OT1
Control output cycle time CT1
Cooling-side control output cycle time
CTc1
UTMD
UTMD
UTMD
OUT
OUT
OUT
Analog output 1 type AO1 UTMD OUT
Main menu Submenu
Operating Parameters
Function Parameter
Preset output n.PO LP1 n.PID
Output limiter
n.POc
LP1 n.PID
Main menu Submenu
Cooling-side preset output
n.OL, n.OH
LP1 n.PID
Note: Parameters n.PO, n.POc, n.OL, n.OH (n=1 to 8) and submenu n.PID (n=1 to 8) correspond to the target setpoint
number selected in the target setpoint number selection (SPNO).
■ Contact Output
Alarm 1 is output via DO1 (contact output 1).
Alarm 2 is output via DO2 (contact output 2).
Alarm 3 is output via DO3 (contact output 3). When cooling-side output is set for relay
output in heating/cooling control, cooling-side output is output via DO3. Alarm 3 is output
via DO5.
Alarm 4 is output via DO4 (contact output 4). When cooling-side output is set for transistor
output in heating/cooling control, cooling-side output is output via DO4. Alarm 4 is output
via DO6.
Alarm 3 is output via DO5 (contact output 5).
Alarm 4 is output via DO6 (contact output 6).
No function is assigned to DO7 (contact output 7).
Setup Parameters
Function Parameter
Alarm 1 type AL1
Alarm 2 type AL2
Alarm 3 type AL3
LOOP1
LOOP1
LOOP1
ALM
ALM
ALM
Alarm 4 type AL4 LOOP1 ALM
Main menu Submenu