EasyManua.ls Logo

York NM120-240 - Air Handling Unit Limitations

York NM120-240
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
505428-YTG-V-0417
Johnson Controls Unitary Products 15
Air Handling Unit Limitations
Model Power Supply Voltage
Voltage Variation Supply Air Range CFM
Entering Air Temperature Degrees °F
Cooling
DB/WB
Heating DB
1
1
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
Min. Max. Min. Max. Min. Max. Min. Max.
NC/NL090
208/230-3-60 187 253 2,250 3,750 65/57 90/77 40 80
460-3-60 414 506 2,250 3,750 65/57 90/77 40 80
575-3-60 540 630 2,250 3,750 65/57 90/77 40 80
NC/NL120
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80
575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
ND/NM120
208/230-3-60 187 253 3,000 5,000 65/57 90/77 40 80
460-3-60 414 506 3,000 5,000 65/57 90/77 40 80
575-3-60 540 630 3,000 5,000 65/57 90/77 40 80
NC/NL180
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
ND/NM180
208/230-3-60 187 253 4,500 7,500 65/57 90/77 40 80
460-3-60 414 506 4,500 7,500 65/57 90/77 40 80
575-3-60 540 630 4,500 7,500 65/57 90/77 40 80
NC/NL240
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
ND/NM240
208/230-3-60 187 253 6,000 10,000 65/57 90/77 40 80
460-3-60 414 506 6,000 10,000 65/57 90/77 40 80
575-3-60 540 630 6,000 10,000 65/57 90/77 40 80
NC/NL300
208/230-3-60 187 253 8,000 12,000 65/57 90/77 40 80
460-3-60 414 506 8,000 12,000 65/57 90/77 40 80
575-3-60 540 630 8,000 12,000 65/57 90/77 40 80

Table of Contents

Related product manuals