505428-YTG-V-0417
Johnson Controls Unitary Products 39
115°F 125°F
2250
77 99.8 8.8 69.7 60.3 50.9 - - - 99.1 9.6 79.9 70.5 61.0 - - -
72 86.5 8.7 71.4 62.0 52.6 43.1 - - 82.7 9.5 75.2 65.7 56.3 46.8 - -
67 73.1 8.7 73.1 63.7 54.2 44.8 35.4 - 66.4 9.5 66.4 60.9 51.5 42.0 32.6 -
62 69.9 8.5 69.9 69.9 62.0 52.6 43.2 33.7 64.9 9.4 64.9 64.9 56.8 47.3 37.9 28.4
57 69.5 8.5 69.5 69.5 60.4 50.9 41.5 32.1 64.1 9.4 64.1 64.1 55.1 45.6 36.2 26.7
2625
77 103.0 8.8 82.4 66.4 55.7 - - - 102.3 9.6 92.7 77.7 67.0 - - -
72 89.2 8.8 78.9 68.2 57.6 46.9 - - 85.4 9.6 83.3 72.6 61.9 51.2 - -
67 75.5 8.7 75.5 70.1 59.4 48.7 38.0 - 68.5 9.6 68.5 67.4 56.7 46.0 35.3 -
62 72.1 8.6 72.1 72.1 67.9 57.3 46.6 35.9 67.0 9.4 67.0 67.0 62.6 52.1 41.2 30.5
57 71.7 8.6 71.7 71.7 66.1 55.4 44.8 34.1 66.2 9.4 66.2 66.2 60.7 50.3 39.3 28.6
3000
77 106.2 8.9 95.1 72.5 60.5 - - - 105.6 9.7 105.6 84.9 73.0 - - -
72 92.0 8.8 86.4 74.5 62.6 50.6 - - 88.1 9.6 88.1 79.4 67.5 55.5 - -
67 77.8 8.7 77.8 76.5 64.6 52.6 40.7 - 70.7 9.6 70.7 70.7 62.0 50.0 38.0 -
62 74.4 8.6 74.4 74.4 73.8 61.9 50.0 38.0 69.2 9.5 69.2 69.2 68.4 56.9 44.5 32.5
57 73.9 8.6 73.9 73.9 71.9 59.9 48.0 36.1 68.3 9.5 68.3 68.3 66.4 54.9 42.4 30.5
3375
72 94.8 8.8 92.1 81.9 68.9 55.9 - - 90.9 9.7 90.9 87.7 74.6 61.5 - -
67 80.2 8.8 80.2 79.6 71.1 58.1 45.1 - 72.9 9.6 72.9 72.9 68.7 55.6 42.5 -
62 76.7 8.6 76.7 76.7 76.4 63.4 50.4 37.4 71.3 9.5 71.3 71.3 71.0 58.1 44.8 31.7
57 76.2 8.6 76.2 76.2 75.2 62.2 49.2 36.2 70.4 9.5 70.4 70.4 69.5 56.7 43.3 30.3
3750
72 97.7 8.8 97.7 89.3 75.2 61.1 - - 93.7 9.7 93.7 93.7 81.8 67.6 - -
67 82.6 8.8 82.6 82.6 77.7 63.6 49.5 - 75.2 9.6 75.2 75.2 75.2 61.2 47.0 -
62 79.0 8.7 79.0 79.0 79.0 64.9 50.8 36.7 73.5 9.5 73.5 73.5 73.5 59.3 45.2 31.0
57 78.5 8.6 78.5 78.5 78.5 64.4 50.3 36.3 72.6 9.5 72.6 72.6 72.6 58.4 44.2 30.0
1
These capacities are gross ratings. For net capacity, deduct supply air blower motor, MBh. Example: Refer to the appropriate Blower
Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746
nameplate rated motor
efficiency.
2
These ratings include the condenser fan motors and the compressor motors but not the supply air blower motor.
PC090/NC090/NL090 Cooling Capacities (Continued)
Air on
Evaporator Coil
Temperature of Air on Condenser Coil
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
Total
Capacity
1
(MBh)
Total
Input
(kW)
2
Sensible Capacity (MBh)
CFM
WB
(°F)
Return Dry Bulb (°F) Return Dry Bulb (°F)
90 85 80 75 70 65 90 85 80 75 70 65