505428-YTG-V-0417
Johnson Controls Unitary Products 71
(NC\ND) 240 C00E (CONSTANT VOLUME)
5.0
208-3-60 14.0
None --- --- --- 17.5 20
20 KW 15 1 41.6 69.5 70
32 KW 24 2 66.6 100.8 110
52 KW 39.1 2 108.5 153.2 175
230-3-60 13.2
None -- --- --- 16.5 20
20 KW 20 1 48.1 76.6 80
32 KW 32 2 77.0 112.7 125
52 KW 52 2 125.1 141.6 150
460-3-60 6.6
None --- --- --- 8.3 15
20 KW 20 1 24.1 38.3 40
32 KW 32 2 38.5 56.4 60
52 KW 52 2 62.5 70.8 80
575-3-60 5.2
None --- --- --- 6.5 15
20 KW 20 1 19.2 30.6 35
32 KW 32 2 30.8 45.0 45
52 KW 52 2 50.0 56.5 60
(NL/NM) 240 C00E (INTELLISPEED)
5.0
208-3-60 13.5
None --- --- --- 16.9 20
20 KW 15 1 41.6 68.9 70
32 KW 24 2 66.6 100.1 110
52 KW 39.1 2 108.5 152.5 175
230-3-60 13.0
None -- --- --- 16.3 20
20 KW 20 1 48.1 76.4 80
32 KW 32 2 77.0 112.5 125
52 KW 52 2 125.1 141.3 150
460-3-60 6.5
None --- --- --- 8.1 15
20 KW 20 1 24.1 38.2 40
32 KW 32 2 38.5 56.2 60
52 KW 52 2 62.5 70.7 80
575-3-60 5.2
None --- --- --- 6.5 15
20 KW 20 1 19.2 30.6 35
32 KW 32 2 30.8 45.0 45
52 KW 52 2 50.0 56.5 60
(NC/NL/ND/NM) 240 C00F (CONSTANT VOLUME & (INTELLISPEED)
7.5
5
208-3-60 20.0
None --- --- --- 25.0 25
20 KW 15 1 41.6 77.0 80
32 KW 24 2 66.6 108.3110
52 KW 39.1 2 108.5 160.7175
230-3-60 19.4
None -- --- --- 24.3 25
20 KW 20 1 48.1 84.4 90
32 KW 32 2 77.0 120.52 125
52 KW 52 2 125.1 149.3 150
460-3-60 9.7
None --- --- --- 12.1 15
20 KW 20 1 24.1 42.2 45
32 KW 32 2 38.5 60.2 70
52 KW 52 2 62.5 74.7 80
575-3-60 7.8
None --- --- --- 9.8 15
20 KW 20 1 19.2 33.8 35
32 KW 32 2 30.8 48.2 50
52 KW 52 2 50.0 59.8 60
1
Minimum Circuit Ampacity.
2
Dual Element, Time Delay Type.
3
HACR type per NEC.
4
(NC/ND)180C00D Models Only
5
NC/ND240C00F Motors Require Overload Relay
Electrical Data - Evaporator Units (Continued)
Motor HP Power Supply
Supply
Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
FLA Model KW Stages Amps

Table of Contents