SECTION 7 - OPERATION
JOHNSON CONTROLS
119
Form 201.28-NM1.1
Issue date: 08/06/2021
7
Address Scale Imperial SI
Point List Description 12345678910
P35 AV29 YT2_ S01_ P35 nvoYTS01p035 SNVT_count_f (51) ADF29 0029 x10 % % Sys 2 Condenser Drain Valve % Open
SSSSSSS
P36 BV5 YT2_ S01_ P36 nvoYTS01p036 SNVT_switch (95)
BD 5 0065 N/A
0/1 0/1 Chiller Run SSSSSSS
P37 BV6 YT2_ S01_ P37 nvoYTS01p037 SNVT_switch (95)
BD 6 0066 N/A
0/1 0/1 Chiller Alarm [0=No Alarm, 1=Alarm] SSSSSSS
P38 BV7 YT2_ S01_ P38 nvoYTS01p038 SNVT_switch (95)
BD 7 0067 N/A
0/1 0/1 Evaporator Heater Status SSSSSSS
P39 BV8 YT2_ S01_ P39 nvoYTS01p039 SNVT_switch (95)
BD 8 0068 N/A
0/1 0/1 Evaporator Pump Status SSSSSSS
P40 BV9 YT2_ S01_ P40 nvoYTS01p040 SNVT_switch (95)
BD 9 0069 N/A
0/1 0/1 Sys 1 Compressor Run Status SSSSSSS
P41 BV10 YT2_ S01_ P41 nvoYTS01p041 SNVT_switch (95)
BD 10 0070 N/A
0/1 0/1 Sys 2 Compressor Run Status SSSSSSS
P42 BV11 YT2_ S01_ P42 nvoYTS01p042 SNVT_switch (95)
BD 11 0071 N/A
0/1 0/1 Sys 1 VI Step Solenoid Valve 1 Status SSSSSSS
P43 BV12 YT2_ S01_ P43 nvoYTS01p043 SNVT_switch (95)
BD 12 0072 N/A
0/1 0/1 Sys 2 VI Step Solenoid Valve 1 Status SSSSSSS
P44 BV13 YT2_ S01_ P44 nvoYTS01p044 SNVT_switch (95)
BD 13 0073 N/A
0/1 0/1 Sys 1 VI Step Solenoid Valve 2 Status SSSSSSS
P45 BV14 YT2_ S01_ P45 nvoYTS01p045 SNVT_switch (95)
BD 14 0074 N/A
0/1 0/1 Sys 2 VI Step Solenoid Valve 2 Status SSSSSSS
P46 BV15 YT2_ S01_ P46 nvoYTS01p046 SNVT_switch (95)
BD 15 0075
NNNNNNN
P47 BV16 YT2_ S01_ P47 nvoYTS01p047 SNVT_switch (95)
BD 16 0076
NNNNNNN
P48 BV17 YT2_ S01_ P48 nvoYTS01p048 SNVT_switch (95)
BD 17 0077
NNNNNNN
P49 BV18 YT2_ S01_ P49 nvoYTS01p049 SNVT_switch (95)
BD 18 0078
NNNNNNN
P50 BV19 YT2_ S01_ P50 nvoYTS01p050 SNVT_switch (95)
BD 19 0079 N/A
0/1 0/1 Cooling Type [0=Water, 1=Glycol] SSSSSSS
P51 BV20 YT2_ S01_ P51 nvoYTS01p051 SNVT_switch (95)
BD 20 0080 N/A
0/1 0/1 Local Remote Control Mode [0=Local, 1=Remote] SSSSSSS
P52 BV21 YT2_ S01_ P52 nvoYTS01p052 SNVT_switch (95)
BD 21 0081 N/A
0/1 0/1 Display Units [0=Imperial, 1=SI] SSSSSSS
P53 BV22 YT2_ S01_ P53 nvoYTS01p053 SNVT_switch (95)
BD 22 0082
NNNNNNN
P54 BV23 YT2_ S01_ P54 nvoYTS01p054 SNVT_switch (95)
BD 23 0083
NNNNNNN
P55 BV24 YT2_ S01_ P55 nvoYTS01p055 SNVT_switch (95)
BD 24 0084
NNNNNNN
P56 MV1 YT2_ S01_ P56 nvoYTS01p056 SNVT_count_f (51)
ADI 1 0030 x1
None None Sys 1 Operational Code SSSSSSS
P57 MV2 YT2_ S01_ P57 nvoYTS01p057 SNVT_count_f (51)
ADI 2 0031 x1
None None Sys 1 Fault Code SSSSSSS
P58 MV3 YT2_ S01_ P58 nvoYTS01p058 SNVT_count_f (51)
ADI 3 0032 x1
None None Sys 2 Operational Code SSSSSSS
P59 MV4 YT2_ S01_ P59 nvoYTS01p059 SNVT_count_f (51)
ADI 4 0033 x1
None None Sys 1 Fault Code SSSSSSS
P60 MV5 YT2_ S01_ P60 nvoYTS01p060 SNVT_count_f (51)
ADI 5 0034 x1
None None Sys 1 Condenser Fan Stage [0-14] SSSSSSS
P61 MV6 YT2_ S01_ P61 nvoYTS01p061 SNVT_count_f (51)
ADI 6 0035 x1
None None Sys 1 Condenser Fan Speed [VSD] OOOOOOO
P62 MV7 YT2_ S01_ P62 nvoYTS01p062 SNVT_count_f (51)
ADI 7 0036 x1
None None Sys 2 Condenser Fan Stage [0-14] SSSSSSS
P63 MV8 YT2_ S01_ P63 nvoYTS01p063 SNVT_count_f (51)
ADI 8 0037 x1
None None Sys 2 Condenser Fan Speed [VSD] OOOOOOO
P64 MV9 YT2_ S01_ P64 nvoYTS01p064 SNVT_count_f (51)
ADI 9 0038 x1
None None Lead System Number SSSSSSS
P65 MV10 YT2_ S01_ P65 nvoYTS01p065 SNVT_count_f (51)
ADI 10 0039
NNNNNNN
P66 AV30 YT2_ S01_ P66 nvoYTS01p066 SNVT_count_f (51)
ADI 11 0040 x10
°F °C Local Leaving Chilled Liquid Setpoint SSSSSSS
P67 AV31 YT2_ S01_ P67 nvoYTS01p067 SNVT_count_f (51)
ADI 12 0041 x10
°F °C Low Leaving Chilled Liquid Temp Cutout SSSSSSS
P68 AV32 YT2_ S01_ P68 nvoYTS01p068 SNVT_count_f (51)
ADI 13 0042 x10
% % Sys 1 Economizer Valve % Open SSSSSSS
P69 AV33 YT2_ S01_ P69 nvoYTS01p069 SNVT_count_f (51)
ADI 14 0043 x10
% % Sys 2 Economizer Valve % Open SSSSSSS
P70 AV34 YT2_ S01_ P70 nvoYTS01p070 SNVT_count_f (51)
ADI 15 0044 x10
PSI BAR Low Suction Pressure Cutout SSSSSSS
P71 AV35 YT2_ S01_ P71 nvoYTS01p071 SNVT_count_f (51)
ADI 16 0045 x10
Volts Volts VSD DC Bus Voltage SSSSSSS
P72 AV36 YT2_ S01_ P72 nvoYTS01p072 SNVT_count_f (51)
ADI 17 0046 x10
°F °C Remote Leaving Chilled Liquid Setpoint SSSSSSS
P73 AV37 YT2_ S01_ P73 nvoYTS01p073 SNVT_count_f (51) ADI 18 0047 x10
°F (diff)
%
°C (diff)
%
Sys 1 Subcooling (Microchannel)
Sys 1 Condenser Level (Round Tube)
SSSSSSS
P74 AV38 YT2_ S01_ P74 nvoYTS01p074 SNVT_count_f (51)
ADI 19 0048 x10
°F °C Cooling Range SSSSSSS
P75 AV39 YT2_ S01_ P75 nvoYTS01p075 SNVT_count_f (51)
ADI 20 0049 x10
°F (diff) °C (diff) Sys 1 Discharge Superheat SSSSSSS
P76 AV40 YT2_ S01_ P76 nvoYTS01p076 SNVT_count_f (51)
ADI 21 0050 x10
°F °C Sys 2 Condenser Temperature SSSSSSS
P77 AV41 YT2_ S01_ P77 nvoYTS01p077 SNVT_count_f (51)
ADI 22 0051 x10
°F °C Sys 2 Discharge Temperature SSSSSSS
P78 AV42 YT2_ S01_ P78 nvoYTS01p078 SNVT_count_f (51) ADI 23 0052 x10
°F (diff)
%
°C (diff)
%
Sys 2 Subcooling (Microchannel)
Sys 2 Condenser Level (Round Tube)
SSSSSSS
P79 AV43 YT2_ S01_ P79 nvoYTS01p079 SNVT_count_f (51)
ADI 24 0053 x10
°F (diff) °C (diff) Sys 2 Discharge Superheat SSSSSSS
P80 BV25 YT2_ S01_ P80 nvoYTS01p080 SNVT_switch (95)
BD 25 0085 N/A
0/1 0/1 Sys 1 Lockout SSSSSSS
P81 BV26 YT2_ S01_ P81 nvoYTS01p081 SNVT_switch (95)
BD 26 0086 N/A
0/1 0/1 Sys 2 Lockout SSSSSSS
P82 BV27 YT2_ S01_ P82 nvoYTS01p082 SNVT_switch (95)
BD 27 0087 N/A
0/1 0/1 Flow Switch Status NNNNNNS
P83 BV28 YT2_ S01_ P83 nvoYTS01p083 SNVT_switch (95)
BD 28 0088
NNNNNNN
YT2_ S01_ P84
nvoYTS01p084 SNVT_switch (95)
0/1 0/1 SCC Auto Detect Available NNSSSSS
LON SNVT Type
N2
Metasys
Units
Point List Code: S = Standard O = Optional N = Not AvailableModbus
Ref
Page
Ref
York Talk Point
Type
LON Profile
Name
Johnson Controls, Inc.
Subject to change without notice.
2 of 5
01/08/20
Table 16 - YVAA E-Link communications data map (cont'd)