Point List Description 12345678910
P03 AV101 YT2_ S02_ P03 nviYTS02p003 SNVT_count_f (51)
ADF 44 0101
NNNNNNN
P04 AV102 YT2_ S02_ P04 nviYTS02p004 SNVT_count_f (51)
ADF 45 0102
NNNNNNN
P05 AV103 YT2_ S02_ P05 nviYTS02p005 SNVT_count_f (51)
ADF 46 0103
NNNNNNN
P06 AV104 YT2_ S02_ P06 nviYTS02p006 SNVT_count_f (51)
ADF 47 0104
NNNNNNN
P07 BV101 YT2_ S02_ P07 nviYTS02p007 SNVT_switch (95)
BD 30 0161
NNNNNNN
P08 BV102 YT2_ S02_ P08 nviYTS02p008 SNVT_switch (95)
BD 31 0162
NNNNNNN
P09 BV103 YT2_ S02_ P09 nviYTS02p009 SNVT_switch (95)
BD 32 0163
NNNNNNN
P10 BV104 YT2_ S02_ P10 nviYTS02p010 SNVT_switch (95)
BD 33 0164
NNNNNNN
P11 AV105 YT2_ S02_ P11 nvoYTS02p011 SNVT_count_f (51)
ADF 48 0105 x10
°F °C Evaporator Entering Liquid Temp (Free Cooling) NNOOOOO
P12 AV106 YT2_ S02_ P12 nvoYTS02p012 SNVT_count_f (51) ADF 49 0106 x10
°F
None
°C
None
Cooling Coil Temperature (Free Cooling Closed Loop)
Unit Input Current
NNNOOOO
P13 AV107 YT2_ S02_ P13 nvoYTS02p013 SNVT_count_f (51)
ADF 50 0107 x10
°F °C Heat Exchanger Leaving Temp (Free Cooling Closed Loop) N N N O O O O
P14 AV108 YT2_ S02_ P14 nvoYTS02p014 SNVT_count_f (51)
ADF 51 0108 x10
°F °C Heat Exchanger Entering Temp (Free Cooling Closed Loop) N N N O O O O
P15 AV109 YT2_ S02_ P15 nvoYTS02p015 SNVT_count_f (51)
ADF 52 0109 x10
% % Glycol Pump Speed (Free Cooling Closed Loop) NNNOOOO
P16 AV110 YT2_ S02_ P16 nvoYTS02p016 SNVT_count_f (51)
ADF 53 0110 x10
% % Cooling Coil Valve (Free Cooling Closed Loop) NNNOOOO
P17 AV111 YT2_ S02_ P17 nvoYTS02p017 SNVT_count_f (51)
ADF 54 0111 x10
% % Cooling Coil Bypass Valve (Free Cooling Closed Loop) N N N O O O O
P18 AV112 YT2_ S02_ P18 nvoYTS02p018 SNVT_count_f (51)
ADF 55 0112 x10
°F °C Sys 1 Suction Temperature (Aggreko) NNNOOOO
P19 AV113 YT2_ S02_ P19 nvoYTS02p019 SNVT_count_f (51)
ADF 56 0113 x10
°F °C Sys 1 Sat Suction Temperature (Aggreko) NNNOOOO
P20 AV114 YT2_ S02_ P20 nvoYTS02p020 SNVT_count_f (51)
ADF 57 0114 x10
°F (diff) °C (diff) Sys 1 Suction Superheat (Aggreko) NNNOOOO
P21 AV115 YT2_ S02_ P21 nvoYTS02p021 SNVT_count_f (51)
ADF 58 0115 x10
% % Sys 1 Flash Trank Drain Valve % (Aggreko) NNNOOOO
P22 AV116 YT2_ S02_ P22 nvoYTS02p022 SNVT_count_f (51)
ADF 59 0116 x10
°F °C Sys 2 Suction Temperature (Aggreko) NNNOOOO
P23 AV117 YT2_ S02_ P23 nvoYTS02p023 SNVT_count_f (51)
ADF 60 0117 x10
°F °C Sys 2 Sat Suction Temperature (Aggreko) NNNOOOO
P24 AV118 YT2_ S02_ P24 nvoYTS02p024 SNVT_count_f (51)
ADF 61 0118 x10
°F (diff) °C (diff) Sys 2 Suction Superheat (Aggreko) NNNOOOO
P25 AV119 YT2_ S02_ P25 nvoYTS02p025 SNVT_count_f (51)
ADF 62 0119 x10
% % Sys 2 Flash Trank Drain Valve % (Aggreko) NNNOOOO
P26 AV120 YT2_ S02_ P26 nvoYTS02p026 SNVT_count_f (51)
ADF 63 0120
NNNNNNN
P27 AV121 YT2_ S02_ P27 nvoYTS02p027 SNVT_count_f (51)
ADF 64 0121
NNNNNNN
P28 AV122 YT2_ S02_ P28 nvoYTS02p028 SNVT_count_f (51)
ADF 65 0122
NNNNNNN
P29 AV123 YT2_ S02_ P29 nvoYTS02p029 SNVT_count_f (51)
ADF 66 0123
NNNNNNN
P30 AV124 YT2_ S02_ P30 nvoYTS02p030 SNVT_count_f (51)
ADF 67 0124
NNNNNNN
P31 AV125 YT2_ S02_ P31 nvoYTS02p031 SNVT_count_f (51)
ADF 68 0125
NNNNNNN
P32 AV126 YT2_ S02_ P32 nvoYTS02p032 SNVT_count_f (51)
ADF 69 0126
NNNNNNN
P33 AV127 YT2_ S02_ P33 nvoYTS02p033 SNVT_count_f (51)
ADF 70 0127 x1
Hz Hz VSD Command Frequency NNSSSSS
P34 AV128 YT2_ S02_ P34 nvoYTS02p034 SNVT_count_f (51)
ADF 71 0128
NNNNNNN
P35 AV129 YT2_ S02_ P35 nvoYTS02p035 SNVT_count_f (51)
ADF 72 0129
NNNNNNN
P36 BV105 YT2_ S02_ P36 nvoYTS02p036 SNVT_switch (95)
BD 34 0165 N/A
0/1 0/1 Option Indicator [0=Disabled, 1=Enabled] NNSSSSS
P37 BV106 YT2_ S02_ P37 nvoYTS02p037 SNVT_switch (95)
BD 35 0166 N/A
0/1 0/1 Free Cooling Valve, if FC OL [0=Off, 1=On] NNOOOOO
P38 BV107 YT2_ S02_ P38 nvoYTS02p038 SNVT_switch (95)
BD 36 0167 N/A
0/1 0/1 Soft Shutdown [0=Disabled, 1=Enabled] NNOOOOO
P39 BV108 YT2_ S02_ P39 nvoYTS02p039 SNVT_switch (95)
BD 37 0168 N/A
0/1 0/1 Remote Evaporator [0=Disabled, 1=Enabled] NNOOOOO
P40 BV109 YT2_ S02_ P40 nvoYTS02p040 SNVT_switch (95)
BD 38 0169 N/A
0/1 0/1 Quick Start [0=Disabled, 1=Enabled] NNOOOOO
P41 BV110 YT2_ S02_ P41 nvoYTS02p041 SNVT_switch (95)
BD 39 0170
NNNNNNN
P42 BV111 YT2_ S02_ P42 nvoYTS02p042 SNVT_switch (95)
BD 40 0171 N/A
0/1 0/1 Glycol Pump Run, if FC CL [0=Off, 1=On] NNNOOOO
P43 BV112 YT2_ S02_ P43 nvoYTS02p043 SNVT_switch (95)
BD 41 0172 N/A
0/1 0/1 Glycol Heater, if FC CL [0=Off, 1=On] NNNOOOO
P44 BV113 YT2_ S02_ P44 nvoYTS02p044 SNVT_switch (95)
BD 42 0173
NNNNNNN
P45 BV114 YT2_ S02_ P45 nvoYTS02p045 SNVT_switch (95)
BD 43 0174
NNNNNNN
P46 BV115 YT2_ S02_ P46 nvoYTS02p046 SNVT_switch (95)
BD 44 0175
NNNNNNN
P47 BV116 YT2_ S02_ P47 nvoYTS02p047 SNVT_switch (95)
BD 45 0176
NNNNNNN
P48 BV117 YT2_ S02_ P48 nvoYTS02p048 SNVT_switch (95)
BD 46 0177 N/A
0/1 0/1 Frame E/F [0=Disabled, 1= Enabled] NNSSSSS
P49 BV118 YT2_ S02_ P49 nvoYTS02p049 SNVT_switch (95)
BD 47 0178 N/A
0/1 0/1 Sound Limit Option [0=Disabled, 1=Enabled] NNSSSSS
P50 BV119 YT2_ S02_ P50 nvoYTS02p050 SNVT_switch (95)
BD 48 0179 N/A
0/1 0/1 SCC Auto Detect Digit 1 NNSSSSS
P51 BV120 YT2_ S02_ P51 nvoYTS02p051 SNVT_switch (95)
BD 49 0180 N/A
0/1 0/1 SCC Auto Detect Digit 2 NNSSSSS
P52 BV121 YT2_ S02_ P52 nvoYTS02p052 SNVT_switch (95)
BD 50 0181 N/A
0/1 0/1 SCC Auto Detect Digit 3 NNSSSSS
P53 BV122
YT2_ S02_ P53
nvoYTS02p053 SNVT_switch (95)
BD 51
0182
N/A
0/1 0/1 SCC Auto Detect Digit 4 NNSSSSS
SECTION 2
Eng
Page
Ref
BACnet
Object
Typ/Ins
BACnet Object
Name
LON Profile
Name
LON SNVT Type
N2
Metasys
Engineering
Units
Point List Code: S = Standard O = Optional N = Not AvailableModbus
YVAA YVFA YAGK BAS
Johnson Controls, Inc.
Subject to change without notice.
3 of 5
01/08/20
Table 16 - YVAA E-Link communications data map (cont'd)

Table of Contents

Related product manuals