SECTION 7 - OPERATION
JOHNSON CONTROLS
121
Form 201.28-NM1.1
Issue date: 08/06/2021
7
Table 16 - YVAA E-Link communications data map (cont'd)
Address Scale Imperial SI
Point List Description 12345678910
P54 BV123 YT2_ S02_ P54 nvoYTS02p054 SNVT_switch (95)
BD 52 0183 N/A
0/1 0/1 SCC Auto Detect Digit 5 NNSSSSS
P55 BV124 YT2_ S02_ P55 nvoYTS02p055 SNVT_switch (95)
BD 53 0184 N/A
0/1 0/1 SCC Auto Detect Digit 6 NNSSSSS
P56 MV101
YT2_ S02_ P56
nvoYTS02p056 SNVT_count_f (51) ADI 11 0130 x1 None None
Condenser Fan Control Type [1=Std. VSD, 2=Opt VSD,
3=Std. Staged, 4=Opt. Staged]
NNSSSSS
P57 MV102 YT2_ S02_ P57 nvoYTS02p057 SNVT_count_f (51) ADI 12 0131 x1 None None Free Cooling Mode, if FC CL or OL [0=M, 1=Fc, 2=Hy] N N O O O O O
P58 MV103
YT2_ S02_ P58
nvoYTS02p058 SNVT_count_f (51)
ADI 13 0132
x1 None None
Free Cooling Control Programmed, if FC CL or OL
[0=Disabled, 1=OL, 2=CL]
NNNOOOO
P59 MV104 YT2_ S02_ P59 nvoYTS02p059 SNVT_count_f (51)
ADI 14 0133
NNNNNNN
P60 MV105 YT2_ S02_ P60 nvoYTS02p060 SNVT_count_f (51)
ADI 15 0134
NNNNNNN
P61 MV106 YT2_ S02_ P61 nvoYTS02p061 SNVT_count_f (51)
ADI 16 0135
NNNNNNN
P62 MV107 YT2_ S02_ P62 nvoYTS02p062 SNVT_count_f (51)
ADI 17 0136
NNNNNNN
P63 MV108 YT2_ S02_ P63 nvoYTS02p063 SNVT_count_f (51)
ADI 18 0137
NNNNNNN
P64 MV109 YT2_ S02_ P64 nvoYTS02p064 SNVT_count_f (51)
ADI 19 0138
NNNNNNN
P65 MV110 YT2_ S02_ P65 nvoYTS02p065 SNVT_count_f (51)
ADI 20 0139
NNNNNNN
P66 AV130 YT2_ S02_ P66 nvoYTS02p066 SNVT_count_f (51)
ADF 73 0140
NNNNNNN
P67 AV131 YT2_ S02_ P67 nvoYTS02p067 SNVT_count_f (51)
ADF 74 0141 x10
None None System 1 Fan Kw NNNNNSS
P68 AV132 YT2_ S02_ P68 nvoYTS02p068 SNVT_count_f (51)
ADF 75 0142 x10
None None System 1 Compressor Kw NNNNNSS
P69 AV133 YT2_ S02_ P69 nvoYTS02p069 SNVT_count_f (51)
ADF 76 0143 x10
None None System 2 Fan Kw NNNNNSS
P70 AV134 YT2_ S02_ P70 nvoYTS02p070 SNVT_count_f (51)
ADF 77 0144 x10
None None System 2 Compressor Kw NNNNNSS
P71 AV135 YT2_ S02_ P71 nvoYTS02p071 SNVT_count_f (51)
ADF 78 0145 x10
Volts Volts DC Bus Voltage 2 (Frame E/F) NNOOOOO
P72 AV136 YT2_ S02_ P72 nvoYTS02p072 SNVT_count_f (51)
ADF 79 0146
NNNNNNN
P73 AV137 YT2_ S02_ P73 nvoYTS02p073 SNVT_count_f (51)
ADF 80 0147
NNNNNNN
P74 AV138 YT2_ S02_ P74 nvoYTS02p074 SNVT_count_f (51)
ADF 81 0148
NNNNNNN
P75 AV139 YT2_ S02_ P75 nvoYTS02p075 SNVT_count_f (51)
ADF 82 0149
NNNNNNN
P76 AV140 YT2_ S02_ P76 nvoYTS02p076 SNVT_count_f (51)
ADF 83 0150
NNNNNNN
P77 AV141 YT2_ S02_ P77 nvoYTS02p077 SNVT_count_f (51)
ADF 84 0151
NNNNNNN
P78 AV142 YT2_ S02_ P78 nvoYTS02p078 SNVT_count_f (51)
ADF 85 0152
NNNNNNN
P79 AV143 YT2_ S02_ P79 nvoYTS02p079 SNVT_count_f (51)
ADF 86 0153
NNNNNNN
P80 BV125 YT2_ S02_ P80 nvoYTS02p080 SNVT_switch (95)
BD 54 0185
NNNNNNN
P81 BV126 YT2_ S02_ P81 nvoYTS02p081 SNVT_switch (95)
BD 55 0186
NNNNNNN
P82 BV127 YT2_ S02_ P82 nvoYTS02p082 SNVT_switch (95)
BD 56 0187
NNNNNNN
P83 BV128 YT2_ S02_ P83 nvoYTS02p083 SNVT_switch (95)
BD 57 0188
NNNNNNN
P84 BV129
YT2_ S02_ P84
nvoYTS02p084 SNVT_switch (95)
BD 58
0189
N/A
0/1 0/1 Units [0=Imperial, 1=Metric] NNSSSSS
1
2
3
4
5
6
7
8
9
10
NOTES
LON SNVTs used: SNVT_count_f (51) and SNVT_switch (95). Must use LON eLink.
Modbus scaling factors indicated in
bold
with an asterisk (*) are user configurable by a field technician, if necessary. All Modbus values are of the type SIGNED with the exception of the user configurable values that
are all UNSIGNED. Modbus function types supported: ENG P03-P06 = Types 03, 06, 16; ENG P07-P10 = 01, 03, 05, 06, 15, 16; ENG P36-P55 & P80-84 = 01, 02, 03
BACnet engineering units shown with an Asterisk (*) will be assigned a BACnet engineering unit type of 95 - No Units.
Status codes: Special display characters such as ( ) [ ] { } / \ % < > are not compatible with eLink N2 formats. Substitute text strings "-", PCT, GTN will be used. String lengths are limited to 60 total characters,
including spaces.
Modbus
Eng
Page
Ref
ASCII
Page
Ref
York Talk Point
Type
LON Profile
Name
LON SNVT Type
N2
Metasys
Engineering
Units
Point List Code: S = Standard O = Optional N = Not Available
YVAA YVFA YAGK BAS 8 JAN 2020
Johnson Controls, Inc.
Subject to change without notice.
4 of 5
01/08/20