SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
75
Form 201.28-NM1.1
Issue date: 08/06/2021
5
All dimensions - in. (mm)
YVAA
A B C D
E-nozzle
size
F G
Water
volume gal
(L)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum
chilled water
ow rate
GPM (L/S)
Frame
Cond.
23 3
15.1
(384)
11.4
(290)
73.3
(1862)
6
56.1
(1425)
58
(220)
250 (16) 980 (62)
24 5
15.3
(389)
11.4
(290)
29.9
(759)
6
56.1
(1425)
71
(269)
300 (19) 1170 (74)
24 8
15.3
(389)
11.4
(290)
122.9
(3122)
6
70
(1778)
71
(269)
300 (19) 1170 (74)
26 3
15.3
(389)
11.4
(290)
117.3
(2979)
6
56.1
(1425)
58
(220)
250 (16) 980 (62)
27 0
15.3
(388)
11.4
(290)
16.8
(427)
6
51.9
(1318)
82
(310)
300 (19) 1170 (74)
27 3
15.3
(389)
11.4
(290)
42.9
(1090)
6
70
(1778)
82
(310)
300 (19) 1170 (74)
27 5
15.5
(394)
14
(356)
44.3
(1125)
8
71.8
(1824)
113
(428)
410 (26) 1600 (101)
27 8
15
(381)
14
(356)
88.3
(2243)
8
71.8
(1824)
113
(428)
410 (26) 1600 (101)
29 5
15.5
(394)
14
(356)
88.3
(2243)
8
71.8
(1824)
113
(428)
410 (26) 1600 (101)
30 3
15.3
(389)
11.4
(290)
122.9
(3122)
6
70
(1778)
71
(269)
300 (19) 1170 (74)
Table 8 - Standard two-pass, rear inlet/outlet evaporator (cont'd)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher.Contact your Johnson Controls Sales O󰀩ce for ratings and further information.