JOHNSON CONTROLS
76
SECTION 5 - TECHNICAL DATA
Form 201.28-NM1.1
Issue date: 08/06/2021
All dimensions - in. (mm)
YVAA
A B C D
E-nozzle
size
F G
Water
volume gal
(L)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum
chilled
water ow
rate GPM
(L/S)
Frame
Cond.
30 5
15.3
(389)
11.4
(290)
166.8
(4237)
6
70
(1778)
71
(269)
300 (19) 1170 (74)
30 8
15.5
(394)
14
(356)
132.2
(3358)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
31 8
15.5
(394)
14
(356)
176.21
(4476)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
32 3
15.5
(394)
14
(356)
88.6
(2250)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
33 3
15.3
(389)
11.4
(290)
166.9
(4239)
6
83.4
(2118)
71
(269)
300 (19) 1170 (74)
34 3
15.5
(394)
14
(356)
132.2
(3358)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
34 5
15.5
(394)
14
(356)
176.2
(4475)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
36 8
16.3
(414)
14
(356)
208.5
(5296)
8
83.4
(2118)
147
(556)
550 (35) 2160 (136)
37 3
15.8
(401)
13
(330)
180.9
(4595)
176.4
(4480)
8
112.2
(2850)
107.7
(2735)
96
(363)
420 (26) 1660 (105)
37 5
16.3
(414)
14
(356)
164.4
(4176)
8
83.4
(2118)
147
(556)
550 (35) 2160 (136)
Table 8 - Standard two-pass, rear inlet/outlet evaporator (cont'd)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales Oce for ratings and further information.