EasyManua.ls Logo

York YVAA Style A - Standard Two-Pass Evaporator Dimensions (Continued); Evaporator Dimensions and Flow Rates (Continued)

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
76
SECTION 5 - TECHNICAL DATA
Form 201.28-NM1.1
Issue date: 08/06/2021
All dimensions - in. (mm)
YVAA
A B C D
E-nozzle
size
F G
Water
volume gal
(L)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum
chilled
water ow
rate GPM
(L/S)
Frame
Cond.
30 5
15.3
(389)
11.4
(290)
166.8
(4237)
6
70
(1778)
71
(269)
300 (19) 1170 (74)
30 8
15.5
(394)
14
(356)
132.2
(3358)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
31 8
15.5
(394)
14
(356)
176.21
(4476)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
32 3
15.5
(394)
14
(356)
88.6
(2250)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
33 3
15.3
(389)
11.4
(290)
166.9
(4239)
6
83.4
(2118)
71
(269)
300 (19) 1170 (74)
34 3
15.5
(394)
14
(356)
132.2
(3358)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
34 5
15.5
(394)
14
(356)
176.2
(4475)
8
83.4
(2118)
113
(428)
410 (26) 1600 (101)
36 8
16.3
(414)
14
(356)
208.5
(5296)
8
83.4
(2118)
147
(556)
550 (35) 2160 (136)
37 3
15.8
(401)
13
(330)
180.9
(4595)
176.4
(4480)
8
112.2
(2850)
107.7
(2735)
96
(363)
420 (26) 1660 (105)
37 5
16.3
(414)
14
(356)
164.4
(4176)
8
83.4
(2118)
147
(556)
550 (35) 2160 (136)
Table 8 - Standard two-pass, rear inlet/outlet evaporator (cont'd)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales O󰀩ce for ratings and further information.