EasyManua.ls Logo

York YVAA Style A - Optional Three-Pass Evaporator Dimensions (Continued); Evaporator Dimensions and Flow Rates (Continued)

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
79
Form 201.28-NM1.1
Issue date: 08/06/2021
5
Table 9 - Optional three-pass rear inlet/front outlet evaporator (cont'd)
All dimensions - in. (mm)
YVAA
A B C D
E- nozzle
size
Water
volume gal
(L)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum chilled
water ow rate
GPM (L/S)
Frame
Cond.
23 3
14.1
(358)
25.5
(648)
73.2
(1859)
56.1
(1425)
5
58
(220)
170 (11) 650 (41)
24 5
15.3
(389)
26.7
(678)
29.9
(759)
56.1
(1425)
6
71
(269)
200 (13) 780 (49)
24 8
15.3
(389)
26.7
(678)
122.9
(3122)
70
(1778)
6
71
(269)
200 (13) 780 (49)
26 3
15.3
(389)
26.7
(678)
117.1
(2974)
56.1
(1425)
5
58
(220)
170 (11) 650 (41)
27 0
15.3
(388)
26.7 (678) 16.8 (427)
51.9
(1318)
6
82
(310)
200 (13) 780 (49)
27 3
15.3
(389)
26.7
(678)
42.9
(1090)
70
(1778)
6
82
(310)
200 (13) 780 (49)
27 5
15.5
(394)
29.5
(749)
88.6
(2250)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
27 8
15.5
(394)
29.5
(749)
88.3
(2243)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
29 5
15.5
(394)
29.5
(749)
88.6
(2250)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
30 3
15.3
(389)
26.7
(678)
122.9
(3122)
70
(1778)
6
71
(269)
200 (13) 780 (49)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales O󰀩ce for ratings and further information.

Table of Contents