EasyManua.ls Logo

York YVAA Style A - Optional Three-Pass Evaporator Dimensions (Continued); Evaporator Dimensions and Flow Rates (Continued)

York YVAA Style A
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
80
SECTION 5 - TECHNICAL DATA
Form 201.28-NM1.1
Issue date: 08/06/2021
All dimensions - in. (mm)
YVAA
A B C D E-nozzle size
Water
volume gal
(L)
Minimum
chilled water
ow rate
GPM (L/S)
Maximum chilled
water ow rate
GPM (L/S)
Frame
Cond.
30 5
15.3
(389)
26.7
(678)
166.9
(4239)
70
(1778)
6
71
(269)
200 (13) 780 (49)
30 8
15
(381)
30.3
(770)
132.2
(3358)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
31 8
15
(381)
29.5
(749)
176.6
(4486)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
32 3
15.5
(394)
29.5
(749)
88.6
(2250)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
33 3
15.3
(389)
26.7
(678)
166.9
(4239)
70
(1778)
6
71
(269)
200 (13) 780 (49)
34 3
15.5
(394)
29.5
(749)
132.6
(3368)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
34 5
15.5
(394)
29.5
(749)
176.2
(4475)
71.8
(1824)
6
113
(428)
270 (17) 1060 (67)
36 8
16.3
(414)
30.3
(770)
208.6
(5298)
83.5
(2121)
8
147
(556)
370 (23) 1440 (91)
37 3
15.8
(401)
28.8
(732)
180.9
(4595)
112.2
(2850)
6
94
(356)
280 (18) 1100 (69)
37 5
16.3
(414)
30.3
(770)
164.3
(4173)
83.4
(2118)
8
147
(556)
370 (23) 1440 (91)
Table 9 - Optional three-pass rear inlet/front outlet evaporator (cont'd)
Note: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Contact your Johnson Controls Sales O󰀩ce for ratings and further information.

Table of Contents