SECTION 6 - OPERATION
OPTIONS KEY
FIGURE 56 - OPTIONS KEY
LD19539
OPTIONS KEY
The OPTIONS key displays unit configuration and the
capability to modify it. To view the current settings,
press this key. Press the or key to scroll to the
next option, and the and keys to change the op-
tions, then the key to save the changes. Each mes-
sage is explained below.
OPTIONS DISPLAY LANGUAGE
◄ ► #####################
Choose English, French, Italian, German, Spanish,
Portuguese, Polish, or Hungarian; default is English.
OPTIONS LIQUID TYPE
◄ ► WATER OR GLYCOL COOLING
OPTIONS LOCAL/REMOTE CONTROL MODE
◄ ► LOCAL OR REMOTE CONTROL
OPTIONS DISPLAY UNITS
◄ ► ENGLISH OR SI
Remote Temperature Reset Input
The display will only appear if the TEMP RESET op-
tion is enabled under UNIT SETUP MODE. Choose
one RESET INPUT below, default is DISABLED:
OPTIONS REMOTE TEMP RESET INPUT
◄ ► DISABLED
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 0.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 2.0 TO 10.0 VOLTS DC
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 0.0 TO 20.0 MILLIAMPS
OPTIONS REMOTE TEMP RESET INPUT
◄ ► 4.0 TO 20.0 MILLIAMPS