EasyManua.ls Logo

AAON RSMV ASM01686 - Sensor Status and Setpoint Status Screens

AAON RSMV ASM01686
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
RSMV Technical Guide
RSMV LCD SCREENS
Sensor Status and Setpoint Status Screens
Sensor Status Screens
Refer to the following map when navigating through the Sensor
Status Screens. From the SENSOR STATUS Screen, press
<ENTER> to scroll through the screens.
Setpoint Status Screens
Refer to the following map when navigating through the Setpoint
Status Screens. From the SETPOINT STATUS Screen, press
<ENTER> to scroll through the screens.
SENSOR
STATUS
SUCTION
XXX PSI
SUCTION PRESSURE READING FROM INPUT
HEAD
XXX PSI
HEAD PRESSURE READING FROM INPUT
SUPRHT 1
XXºF
CURRENT SUPERHEAT 1 CALCULATION
SUPRHT 2
XXºF
CURRENT SUPERHEAT 2 CALCULATION
COIL 1
XXºF
COIL TEMPERATURE 1 READING FROM
TEMPERATURE SENSOR INPUT
COIL 2
XXºF
COIL TEMPERATURE 2 READING FROM
TEMPERATURE SENSOR INPUT
CALC CT
XXºF
CALCULATED COIL TEMPERATURE FROM
SUCTION PRESSURE INPUT
SETPOINT
STATUS
HEADPRSP
340 PSI
HEAD PRESSURE SETPOINT
Valid range is 275 to 475 PSI. Default is 340 PSI.
SPRHT SP
15ºF
SUPERHEAT SETPOINT SETTING
Valid range is 1ºF to 30ºF. Default is 15ºF.

Table of Contents