Ascotel® IntelliGate® 150/300 as of I7.9
68 Installation
syd-0210/1.7 – I7.9 – 12.2009
4. 2. 7. 1 Rack-mounting procedure
Materials required:
• Rack-mounting set for A150 and A300
• Screw set for wall/desktop installation
• Screwdriver
For the rack-mounting of the A150/300 proceed as follows:
1. Pull off the screw covers on the left and right of the front panel.
2. Secure the mounting plates to the basic system using the M4 screws. Make sure
the front panel and the mounting plate are aligned.
3. Disconnect the system from the power supply.
Warning
Be sure to observe the "Safety regulations", page 61.
4. Remove the housing cover.
5. A300 only:
Install the fan (see "Installing the fan", page 69).
6. Connect the earthing (see "Connecting the earthing", page 72).
7. Fit the housing cover.
8. Secure the cage nuts in the appropriate positions in the rack’s fastening rails (see
Fig. 20).
9. Secure the basic system to the rack’s fastening rails using the M6 screws, the
plastic washers and the cage nuts.
10.Fasten the snap-on tag to the front panel.
11.Reconnect the system to the power supply.