Class Comp Dev Mod Ch Err PS501
PLC
Browser
<− Display in
Class Interface Device Module Channel Error
Identifier
Error message Remedy
1
)
2
)
3
)
4
)
3 14 1...10 31 31 26 Parameter error Check
master
11 / 12 ADR 1...10
Remarks:
1
)
In AC500 the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The PNIO diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself,
1...10 = decentralized communication interface module 1...10,
ADR = hardware address (e. g. of the DC551-CS31)
3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
4
)
In case of module errors, with channel "31 = module itself" is output.
6.2.2.7 State LEDs
LED State Color LED = OFF LED = ON
Outputs O0...O3 Digital output Yellow Output is OFF Output is ON
(The output
voltage (normally
24 VDC) is only
displayed if UP/ZP
and L+/M (supply
voltages for the
module) are
switched ON)
6.2.2.8 Technical data
The system data of AC500-eCo V3 apply
Ä
Chapter 6.4 “System data AC500-eCo V3”
on page 154
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 6 for UP (+24 V DC) and terminal 7
for ZP (0 V DC)
Device specifications
Option boards > TA5105-4DOT - Digital output module option board
2021/06/293ADR010635, 2, en_US114