1. Double-click “PLC_AC500_V3” in the device tree.
2. Select “Communication Settings”.
ð
The selected IP address is shown.
3. If the IP address is not visible, enter the IP address manually.
4. To test the connection and/or to see the CPU information press [Enter] or click on the
black dot next to the PLC picture.
5.4.6 AC500 V3 firmware installation and update
The PLC firmware can be updated via Automation Builder.
This is also necessary for commissioning AC500-eCo V3 CPUs.
A very new CPU has no pre-installed firmware. To guarantee the authenticity of delivered
AC500 firmware, V3 CPUs are delivered with a boot loader only. You need to download a valid
firmware to the CPU. After download, the functionality of the CPU is given.
An Automation Builder project with an AC500 V3 CPU is open.
CPU is in "stop" mode without firmware.
The power LED is ON.
Getting Started
Example project > AC500 V3 firmware installation and update