DiagCode State Name State Description and Output Setting
8014 Wait for NC ChannelNO has been switched to FALSE - waiting for ChannelNC to be
switched to TRUE; discrepancy timer started.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE
8005 From Active
Wait
One channel has been switched to inactive; waiting for the second channel
to be switched to inactive too.
Ready = TRUE
S_AntivalentOut = FALSE
Error = FALSE
4.6.6.4 SF_ModeSelector
Standards Requirements
MRL 98/37/EC,
Annex I
1.2.3. Starting
… It must be possible to start machinery only by voluntary actuation of a control pro-
vided for the purpose …The same requirement applies: …
- when effecting a significant change in the operating conditions …
1.2.5 … mode selector which can be locked in each position. Each position of the
selector must correspond to a single operating or control mode …
EN ISO 12100-2:
2003
4.11.10 Selection of Control and Operating Modes
… shall be fitted with a mode selector which can be locked in each position. Each posi-
tion of the selector shall be clearly identifiable and shall exclusively enable one control
or operating mode to be selected…
IEC 60204-1, Ed.
5.0 : 2003
9.2.3 Operating Modes
… When a hazardous condition can result from a mode selection, unauthorized and/or
inadvertent selection shall be prevented by suitable means (e.g. key operated switch,
access code). Mode selection by itself shall not initiate machine operation. A separate
action by the operator shall be required. … Indication of the selected operating mode
shall be provided …
EN 954-1: 1996 5.4 Manual reset
ISO 12100-2:
2003
4.11.4: Restart following power failure/spontaneous restart
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 279