3.4.9.3 Technical data of non-safety test pulse outputs
Data Value Unit
Number of test pulse channels per module (transistor test pulse
outputs)
4
Terminals of the channels T0, T1 1.0, 1.2
Terminals of the channels T2 to T3 3.0, 3.2
Terminals of reference potential for all test pulse outputs (minus
pole of the process supply voltage, signal name ZP)
1.9 … 4.9
Terminals of common power supply voltage for all outputs (plus
pole of the process supply voltage, signal name UP)
1.8 … 4.8
Output voltage for signal 1 UP – 0.8 V
Length of test pulse 0 phase 1 ms
Output current
Data Value Unit
Rated value, per channel 10 mA
Maximum value (all channels together) 40 mA
Short-circuit proof / overload proof yes
Output current limitation 65 mA
Resistance to feedback against 24V signals yes
Cable length
Data Value Unit
Max. cable length, shielded 1000 m
Max. cable length, unshielded 600 m
3.4.10 Ordering data
Type Description Order code
DX581-S DX581-S:S500, Safety Digital I/O
Module 8SDI/SDO
1SAP 284 100 R0001
DX581-S-XC DX581-S-XC:S500, Safety Digital I/O
Module 8SDI/SDO, Extreme Condi-
tions
1SAP 484 100 R0001
AC500-S Safety Modules
DX581-S digital safety input/output module > Ordering data
30.03.2017 AC500-S 135