“Warmstart on E2 failure” parameter setting of PM5xx Non-safety CPU has the following influence on the
SM560-S:
n “Off” (Default)
In case of severe error (E2), no warm restart of PM5xx and of all its communication modules, including
SM560-S Safety CPU, will be done.
n “On” (after E2 error and / or after short voltage dip)
In case of severe error (E2) and or short voltage dip, the warm restart of PM5xx and of all its communica-
tion modules, including SM560-S Safety CPU, will be done. After restart of SM560-S Safety CPU, Safety
I/O can be reintegrated using PROFIsafe F-Device reintegration scheme [3].
3.1.7 Technical data
Use SM560-S Safety CPU (up to SIL3 and PL e) with PM573, PM583, PM592 or others with the firmware
version from V2.2.1 (pay attention to the required TB units). SM560-S Safety CPU shall not to be used with
AC500-eCo CPUs.
NOTICE!
SM560-S-XC version is available for usage in extreme environmental conditions (
Ä
Appendix
“System data for AC500-S-XC” on page 446).
AC500-S Safety Modules
SM560-S Safety CPU > Technical data