Fig. 138: Access protection at a material gate - Application Program Page 2
7.3.5 Additional notes
In this example, two contacts of the guard switch are connected to a safety input device, which realizes the
error detection. The resulting BOOL signal is mapped to the two input channels of the SF_GuardMoni-
toring_1.
The diagnostic information retrieval has not been covered in this example. For this, refer to
Ä
Chapter 7.2.5
“Additional notes” on page 428. The input parameter Activate for the dynamic FB activation has been set to
TRUE for clarity sake. However, in an application, this can be replaced by a variable.