Table 42: FB Name: SF_ModeSelector
Name Data Type Initial Value Description, Parameter Values
VAR_INPUT
Activate BOOL FALSE
Ä
Table 31 “General Input Parameters”
on page 266
S_Mode0 BOOL FALSE Variable or constant.
Input 0 from mode selector switch
FALSE: Mode 0 is not requested by operator.
TRUE: Mode 0 is requested by operator.
S_Mode1 BOOL FALSE Variable or constant.
Input 1 from mode selector switch
FALSE: Mode 1 is not requested by operator.
TRUE: Mode 1 is requested by operator.
S_Mode2 BOOL FALSE Variable or constant.
Input 2 from mode selector switch
FALSE: Mode 2 is not requested by operator.
TRUE: Mode 2 is requested by operator.
S_Mode3 BOOL FALSE Variable or constant.
Input 3 from mode selector switch
FALSE: Mode 3 is not requested by operator.
TRUE: Mode 3 is requested by operator.
S_Mode4 BOOL FALSE Variable or constant.
Input 4 from mode selector switch
FALSE: Mode 4 is not requested by operator.
TRUE: Mode 4 is requested by operator.
S_Mode5 BOOL FALSE Variable or constant.
Input 5 from mode selector switch
FALSE: Mode 5 is not requested by operator.
TRUE: Mode 5 is requested by operator.
S_Mode6 BOOL FALSE Variable or constant.
Input 6 from mode selector switch
FALSE: Mode 6 is not requested by operator.
TRUE: Mode 6 is requested by operator.
S_Mode7 BOOL FALSE Variable or constant.
Input 7 from mode selector switch
FALSE: Mode 7 is not requested by operator.
TRUE: Mode 7 is requested by operator.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 281