Name Data Type Initial Value Description, Parameter Values
S_OSSD_Out BOOL FALSE Safety related output indicating the status of the
ESPE.
FALSE: The sensor has a safety-related action
request or test error. TRUE: The sensor has no
safety-related action request and no test error.
S_TestOut BOOL TRUE Coupled with the test input of the sensor.
FALSE: Test request issued.
TRUE: No test request.
TestPossible BOOL FALSE Feedback signal to the process.
FALSE: An automatic sensor test is not possible.
TRUE: An automatic sensor test is possible.
TestExecuted BOOL FALSE A positive signal edge indicates the successful
execution of the automatic sensor test.
FALSE:
- An automatic sensor test was not executed yet.
- An automatic sensor test is active.
- An automatic sensor test was faulty.
TRUE: A sensor test was executed successfully.
Error BOOL FALSE
Ä
Table 32 “General Output Parameters”
on page 267
DiagCode WORD 16#0000
Ä
Table 32 “General Output Parameters”
on page 267
Notes: OSSD: Output Signal Switching Device.
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib