DiagCode State Name State Description and Output Setting
8012 ESPE Inter-
rupted 2
The FB has detected a safety demand.
The switch was automatically tested.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = FALSE
8013 Wait for Reset
2
Wait for rising trigger of Reset after state 8012.
Ready = TRUE
S_OSSD_Out = FALSE
S_TestOut = TRUE
TestPossible = FALSE
TestExecuted = TRUE
Error = FALSE
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017 AC500-S 333