MutingEnable AND (R_TRIG at MS_11 AND NOT MS_12 AND NOT MS_21 AND NOT MS_22)
Muting condition 2 (from 8011 to 8012) (MS_12 is the second entry switch actuated):
MutingEnable AND (MS_11 AND R_TRIG at MS_12 AND NOT MS_21 AND NOT MS_22)
Muting condition 3 (from 8012 to 8000) (MS_21 is the first exit switch released). Stop timer MaxMutingTime:
NOT MS_11 AND NOT MS_12 AND F_TRIG at MS_21 AND MS_22
Backward Direction
Muting condition 11 (to 8122) (MS_22 is the first entry switch actuated). Start timer MaxMutingTime:
MutingEnable AND (NOT MS_11 AND NOT MS_12 AND NOT MS_21 AND R_TRIG at MS_22)
Muting condition 12 (from 8122 to 8112) (MS_21 is the second entry switch actuated):
MutingEnable AND (NOT MS_11 AND NOT MS_12 AND R_TRIG at MS_21 AND MS_22)
Muting condition 13 (MS_12 is the first exit switch released). Stop timer MaxMutingTime:
MS_11 AND F_TRIG at MS_12 AND NOT MS_21 AND NOT MS_22
Specification of wrong MutingSequences:
In state 8000 - (NOT MutingEnable AND R_TRIG at MS_11) OR (NOT MutingEnable AND R_TRIG at
MS_22) OR (MS_12 OR MS_21) OR (MS_11 AND MS_22)
In state 8011 - NOT MutingEnable OR NOT MS_11 OR MS_21 OR MS_22
In state 8012 - R_TRIG at MS_11 OR R_TRIG at MS_12 OR F_TRIG at MS_22
In state 8122 - NOT MutingEnable OR MS_11 OR MS_12 OR NOT MS_22
In state 8112 - F_TRIG at MS_11 OR R_TRIG at MS_21 OR R_TRIG at MS_22
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib